ASEA BROWN BOVERI 1SDA066433R1 - Molded Case Circuit Breaker
This component is a 3-pole Molded Case Circuit Breaker from the ABB SACE Tmax XT2 series, engineered for overcurrent and short-circuit protection in industrial and commercial electrical distribution systems. It integrates a fixed thermal-magnetic trip unit, providing reliable protection for conductors, motors, and general loads within switchboards and control panels. The device is designed for fixed installation with front terminal connections, ensuring robust performance in demanding industrial environments.
Technical Specifications:
- SERIES/FAMILY: ABB SACE Tmax XT2
- COMPONENT TYPE: Molded Case Circuit Breaker (MCCB)
- ELECTRICAL SPECS:
- NOMINAL CURRENT (In): 160A
- NUMBER OF POLES: 3-pole
- RATED OPERATIONAL VOLTAGE (Ue): 400/415VAC, 500VAC, 690VAC
- RATED INSULATION VOLTAGE (Ui): 1000V
- RATED IMPULSE WITHSTAND VOLTAGE (Uimp): 8kV
- RATED ULTIMATE SHORT-CIRCUIT BREAKING CAPACITY (Icu) at 400/415VAC: 36kA
- RATED SERVICE SHORT-CIRCUIT BREAKING CAPACITY (Ics) at 400/415VAC: 36kA
- FREQUENCY: 50/60 Hz
- TRIP UNIT TYPE: Thermal Magnetic (TMD)
- THERMAL PROTECTION (Ir): Adjustable from 0.7 to 1.0 x In
- MAGNETIC PROTECTION (Ii): Fixed at 10 x In
- MECHANICAL/PHYSICAL:
- FRAME SIZE: XT2
- MOUNTING TYPE: Fixed
- TERMINAL TYPE: Front terminals
- MECHANICAL ENDURANCE: 20000 cycles
- INTERFACE/CONTROL:
- AUXILIARY PROVISION: Designed for integration of optional auxiliary contacts, shunt trips, and undervoltage releases
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20 (terminals)
- COOLING METHOD: Natural air convection
- MOUNTING STYLE: Panel mounted, fixed
- COMPATIBILITY/APPLICATION:
- TARGET SYSTEMS: Industrial and commercial electrical distribution boards, motor control centers, machinery protection
- APPLICATION: Overcurrent and short-circuit protection for cables, motors, transformers, and general electrical loads