PRODUCT DESCRIPTION
ASEA BROWN BOVERI 1SDA073753R1 - Molded Case Circuit Breaker
This component is an ABB SACE Tmax XT2N series molded case circuit breaker, engineered for robust electrical circuit protection in industrial and commercial power distribution systems. It integrates a thermal-magnetic trip unit to provide reliable overload and short-circuit protection for conductors, motors, and transformers. Designed for fixed installation with front terminals, this device ensures compliance with international electrical safety standards for critical infrastructure applications.
Technical Specifications:
- SERIES/FAMILY: SACE Tmax XT2N
- COMPONENT TYPE: Molded Case Circuit Breaker (MCCB)
- ELECTRICAL SPECS:
- NOMINAL CURRENT (In): 160A
- POLES: 3-pole
- NOMINAL OPERATIONAL VOLTAGE (Ue): Up to 690VAC
- NOMINAL INSULATION VOLTAGE (Ui): 1000V
- NOMINAL IMPULSE WITHSTAND VOLTAGE (Uimp): 8kV
- NOMINAL ULTIMATE SHORT-CIRCUIT BREAKING CAPACITY (Icu): 36kA at 400/415VAC
- NOMINAL SERVICE SHORT-CIRCUIT BREAKING CAPACITY (Ics): 36kA at 400/415VAC (100% of Icu)
- FREQUENCY: 50/60 Hz
- MECHANICAL/PHYSICAL:
- TRIP UNIT TYPE: Thermal-Magnetic (TMD)
- MOUNTING TYPE: Fixed
- TERMINAL TYPE: Front terminals
- FRAME SIZE: XT2
- INTERFACE/CONTROL:
- PROTECTION FUNCTIONS: Overload protection (thermal), Short-circuit protection (instantaneous magnetic)
- THERMAL TRIP ADJUSTMENT (Ir): Adjustable from 0.7 to 1.0 x In (112A to 160A)
- MAGNETIC TRIP SETTING (Ii): Fixed at 10 x In (1600A)
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20 (terminals), IP40 (front with suitable enclosure)
- COOLING METHOD: Natural air convection
- OPERATING TEMPERATURE: -25 to +70 degrees Celsius
- COMPATIBILITY/APPLICATION:
- APPLICATIONS: Industrial power distribution, commercial building electrical systems, motor protection, transformer protection, generator protection.
- STANDARDS: IEC 60947-2