ASEA BROWN BOVERI 1SDA104813R1 - Molded Case Circuit Breaker
This is an ABB SACE Tmax XT2N series molded case circuit breaker, engineered for robust overcurrent and short-circuit protection in industrial and commercial low-voltage distribution systems. It integrates an advanced PR221DS electronic trip unit, providing precise LSI (Long-time, Short-time, Instantaneous) protection for enhanced system reliability and selective coordination. This device is designed for critical power distribution applications, motor protection, and generator protection within switchgear and control panels.
Technical Specifications:
- SERIES/FAMILY: SACE Tmax XT2N
- COMPONENT TYPE: Molded Case Circuit Breaker (MCCB)
- ELECTRICAL SPECS:
- NOMINAL CURRENT (In): 160A
- NUMBER OF POLES: 3
- RATED OPERATIONAL VOLTAGE (Ue): 690VAC
- RATED INSULATION VOLTAGE (Ui): 1000V
- RATED IMPULSE WITHSTAND VOLTAGE (Uimp): 8kV
- RATED SHORT-CIRCUIT BREAKING CAPACITY (Icu): 36kA at 400VAC
- TRIP UNIT TYPE: Electronic
- TRIP UNIT MODEL: PR221DS
- PROTECTION FUNCTIONS: L (Long-time overload), S (Short-time short-circuit), I (Instantaneous short-circuit)
- MECHANICAL/PHYSICAL:
- FRAME SIZE: XT2 (Up to 160A)
- MOUNTING TYPE: Fixed
- TERMINAL TYPE: Front
- OPERATING MECHANISM: Toggle
- INTERFACE/CONTROL:
- TRIP UNIT ADJUSTABILITY: Electronic settings for L, S, I thresholds and delays via local interface
- AUXILIARY CONTACTS: Optional (accessory dependent)
- COMMUNICATION: Not inherent in base unit higher-end trip units in series support fieldbus protocols
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20 (with terminal covers)
- COOLING METHOD: Natural air convection
- OPERATING TEMPERATURE: -25 to +70 degrees Celsius
- STORAGE TEMPERATURE: -40 to +85 degrees Celsius
- MOUNTING STYLE: Panel mounted within enclosure
- COMPATIBILITY/APPLICATION:
- TARGET SYSTEMS: Low-voltage power distribution, industrial control panels, switchgear, motor control centers (MCCs)
- APPLICATIONS: Overload and short-circuit protection for feeders, branch circuits, motors, and transformers in commercial and industrial facilities.