PRODUCT DESCRIPTION
ASEA BROWN BOVERI 1SDA104895R1 - Low Voltage Air Circuit Breaker
This device is an ASEA BROWN BOVERI SACE Emax 2 series low voltage air circuit breaker, model E2.2N, engineered for robust protection of industrial electrical distribution systems. Rated for 1600A, it integrates an advanced PR121/P electronic trip unit providing Long-time, Short-time, Instantaneous, and Residual current protection. It is designed for main incoming, feeder, and generator protection applications requiring high breaking capacity and precise fault discrimination.
Technical Specifications:
- SERIES/FAMILY: SACE Emax 2
- COMPONENT TYPE: Low Voltage Air Circuit Breaker (ACB)
- ELECTRICAL SPECS:
- RATED CURRENT (In): 1600A
- FRAME SIZE: E2.2 (Rated up to 2000A)
- RATED OPERATIONAL VOLTAGE (Ue): Up to 690VAC
- RATED INSULATION VOLTAGE (Ui): 1000V
- RATED IMPULSE WITHSTAND VOLTAGE (Uimp): 8kV
- RATED FREQUENCY: 50/60 Hz
- RATED ULTIMATE SHORT-CIRCUIT BREAKING CAPACITY (Icu): 50kA at 400/415VAC
- RATED SERVICE SHORT-CIRCUIT BREAKING CAPACITY (Ics): 50kA at 400/415VAC
- MECHANICAL/PHYSICAL:
- MOUNTING TYPE: Fixed
- OPERATING MECHANISM: Manual Front-Operated
- MECHANICAL ENDURANCE: 10,000 cycles
- INTERFACE/CONTROL:
- TRIP UNIT: PR121/P Electronic Trip Unit
- PROTECTION FUNCTIONS: Long-time (L), Short-time (S), Instantaneous (I), Residual Current (R)
- COMMUNICATION CAPABILITY: Supports optional Ekip Com communication modules (e.g., Modbus RTU, Profibus DP, DeviceNet, Ethernet/IP, PROFINET)
- FEEDBACK: Integrated status and alarm indications via trip unit
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP30 (front), IP20 (terminals) when installed in enclosure
- COOLING METHOD: Natural Air Convection
- OPERATING TEMPERATURE RANGE: -25 to +70 degrees C
- COMPATIBILITY/APPLICATION:
- TARGET SYSTEMS: Industrial power distribution networks, Motor Control Centers (MCCs), Generator protection, Main and sub-distribution switchboards
- COMPLIANCE: IEC 60947-2