PRODUCT DESCRIPTION
ASEA BROWN BOVERI 1SDA104958R1 - Molded Case Circuit Breaker
This component is an ABB SACE Tmax XT2N series molded case circuit breaker, engineered for robust electrical circuit protection in industrial and commercial low-voltage power distribution systems. It integrates a fixed thermal-magnetic trip unit to provide reliable overload and short-circuit protection for critical infrastructure, including motor circuits, generator outputs, and transformer secondary lines. This device is essential for maintaining system integrity and operational safety in demanding industrial environments.
Technical Specifications:
- SERIES/FAMILY: SACE Tmax XT2N
- COMPONENT TYPE: Molded Case Circuit Breaker (MCCB)
- ELECTRICAL SPECS:
- NOMINAL CURRENT (In): 160A
- POLES: 3
- TRIP UNIT TYPE: Thermal Magnetic Fixed (TMD)
- RATED OPERATIONAL VOLTAGE (Ue): 690VAC
- RATED INSULATION VOLTAGE (Ui): 1000V
- RATED IMPULSE WITHSTAND VOLTAGE (Uimp): 8kV
- RATED FREQUENCY: 50/60 Hz
- RATED ULTIMATE SHORT-CIRCUIT BREAKING CAPACITY (Icu) at 400VAC: 36kA
- RATED SERVICE SHORT-CIRCUIT BREAKING CAPACITY (Ics) at 400VAC: 36kA
- THERMAL PROTECTION THRESHOLD: Fixed at 1.0 x In (160A)
- MAGNETIC PROTECTION THRESHOLD: Fixed at 10 x In (1600A)
- MECHANICAL/PHYSICAL:
- FRAME SIZE: XT2
- MOUNTING TYPE: Fixed
- TERMINAL TYPE: Front terminals
- MECHANICAL ENDURANCE: 20000 cycles
- ELECTRICAL ENDURANCE: 8000 cycles (at In)
- INTERFACE/CONTROL:
- TRIP UNIT ADJUSTMENT: Non-adjustable fixed thresholds
- INDICATORS: Mechanical trip indicator
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20 (with terminal covers)
- OPERATING TEMPERATURE RANGE: -25 to +70 degrees C
- STORAGE TEMPERATURE RANGE: -40 to +85 degrees C
- MOUNTING POSITION: Vertical or horizontal
- COMPATIBILITY/APPLICATION:
- APPLICATIONS: Low-voltage power distribution, motor protection, generator protection, transformer protection, industrial machinery, commercial building infrastructure
- STANDARDS COMPLIANCE: IEC 60947-2