PRODUCT DESCRIPTION
ASEA BROWN BOVERI 1SDA105117R1 - Molded Case Circuit Breaker
This device is an ABB SACE Tmax XT2N series molded case circuit breaker, engineered for reliable overcurrent and short-circuit protection in low-voltage electrical distribution systems. It integrates a thermal-magnetic trip unit to safeguard industrial and commercial circuits against overload conditions and instantaneous short-circuit faults. The unit is designed for fixed installation within switchboards, control panels, and motor control centers, ensuring operational continuity and system integrity.
Technical Specifications:
- SERIES/FAMILY: SACE Tmax XT2N
- COMPONENT TYPE: Molded Case Circuit Breaker (MCCB)
- ELECTRICAL SPECS:
- NOMINAL CURRENT (In): 160A
- POLES: 3
- RATED OPERATIONAL VOLTAGE (Ue): Up to 690VAC
- RATED INSULATION VOLTAGE (Ui): 1000V
- RATED IMPULSE WITHSTAND VOLTAGE (Uimp): 8kV
- RATED FREQUENCY: 50/60 Hz
- RATED ULTIMATE SHORT-CIRCUIT BREAKING CAPACITY (Icu): 36kA at 400/415VAC
- MECHANICAL/PHYSICAL:
- FRAME SIZE: XT2 (160A frame)
- MOUNTING TYPE: Fixed
- TERMINAL TYPE: Front terminals
- INTERFACE/CONTROL:
- TRIP UNIT TYPE: Thermal Magnetic Disconnect (TMD)
- TRIP UNIT FUNCTION: Overload protection (thermal), Short-circuit protection (magnetic)
- THERMAL PROTECTION ADJUSTMENT (Ir): 0.7 to 1.0 x In
- MAGNETIC PROTECTION SETTING (Ii): 10 x In (fixed)
- ENVIRONMENTAL/MOUNTING:
- PROTECTION DEGREE (TERMINALS): IP20
- PROTECTION DEGREE (FRONT): IP30 (with standard accessories)
- COOLING METHOD: Natural convection
- MOUNTING POSITION: Vertical or horizontal
- COMPATIBILITY/APPLICATION:
- APPLICATION SEGMENTS: Industrial power distribution, commercial building infrastructure, motor control centers, switchgear
- COMPLIANCE STANDARD: IEC 60947-2