PRODUCT DESCRIPTION
ASEA BROWN BOVERI 2CSF202568R1160 - Residual Current Device (RCD)
This device is an ABB F200 series Residual Current Device, engineered for protection against earth leakage currents in industrial and commercial electrical installations. It provides critical safety functionality by rapidly disconnecting the circuit upon detection of a fault, mitigating risks of electric shock and fire. The unit is designed for integration into low-voltage distribution systems, ensuring compliance with electrical safety standards in applications such as machinery control, power distribution panels, and building automation.
Technical Specifications:
- SERIES/FAMILY: F200 Series, System pro M compact
- COMPONENT TYPE: Residual Current Device (RCD)
- ELECTRICAL SPECS:
- NOMINAL VOLTAGE: 230/400 VAC
- RATED CURRENT: 16 A
- RATED RESIDUAL OPERATING CURRENT: 0.03 A (30 mA)
- RATED FREQUENCY: 50/60 Hz
- NUMBER OF POLES: 2
- RESIDUAL CURRENT TYPE: AC (Alternating Current sensitive)
- RATED SHORT-CIRCUIT CAPACITY: 6 kA
- RATED CONDITIONAL SHORT-CIRCUIT CURRENT: 6 kA
- MECHANICAL/PHYSICAL:
- MOUNTING TYPE: DIN Rail
- TERMINAL TYPE: Screw
- TERMINAL CAPACITY: 25 mm² (Solid/Stranded), 16 mm² (Flexible)
- MODULE WIDTH: 2 modules (35 mm)
- INTERFACE/CONTROL:
- INDICATION: ON/OFF position, Trip status
- TEST FUNCTION: Integrated test button
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20 (Terminals), IP40 (Enclosure with cover)
- OPERATING TEMPERATURE: -25 to +55 degrees C
- STORAGE TEMPERATURE: -40 to +70 degrees C
- COOLING METHOD: Natural convection
- COMPATIBILITY/APPLICATION:
- APPLICATION: Protection against earth leakage currents, electric shock, and fire in low-voltage distribution systems.
- STANDARDS: IEC/EN 61008-1