The ALLEN BRADLEY 140G series comprises compact motor protection circuit breakers engineered for the control and protection of electric motors and other inductive loads. These devices integrate thermal overload protection, magnetic short-circuit protection, and manual switching functions into a single unit. They are designed for industrial applications requiring reliable motor control, fault isolation, and compliance with international protection standards within control panels and machinery.
Technical Specifications:
- SERIES/FAMILY: 140G
- COMPONENT TYPE: Motor Protection Circuit Breaker (MPCB)
- ELECTRICAL SPECS:
- RATED OPERATIONAL VOLTAGE: Up to 690VAC
- THERMAL TRIP ADJUSTMENT RANGE: 0.63 - 1.0A
- MAGNETIC TRIP CURRENT: Approximately 13x In (e.g., 13A for 1.0A thermal setting)
- SHORT-CIRCUIT BREAKING CAPACITY (Icu): 50kA at 400VAC (typical for M-frame)
- FREQUENCY: 50/60 Hz
- PHASE: Multi-phase (typically 3-phase)
- MECHANICAL/PHYSICAL:
- FRAME SIZE: M-Frame
- OPERATION: Manual ON/OFF switching with trip indication
- AUXILIARY CONTACTS: Not integrated into base unit external modules available
- INTERFACE/CONTROL:
- TRIP MECHANISM: Thermal-magnetic
- CONTROL TYPE: Manual rotary handle
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20 (terminals), IP40 (front with appropriate enclosure)
- MOUNTING STYLE: 35mm DIN Rail
- OPERATING TEMPERATURE: -20°C to +60°C
- COMPATIBILITY/APPLICATION:
- TARGET SYSTEMS: Industrial motor control circuits, HVAC systems, pump stations, conveyor systems, machine tools
- FUNCTION: Overload protection, short-circuit protection, manual motor control, phase loss protection for motors up to 1.0A nominal current