PRODUCT DESCRIPTION
HONEYWELL R4343D1017 - Intermittent Pilot Oil/Gas Primary Control
This primary safety control from the R4343D series is engineered for intermittent pilot operation in commercial and industrial oil or gas burner applications. It provides precise ignition sequencing, continuous flame supervision, and system lockout upon detected flame failure, ensuring safe and compliant burner operation. The unit integrates with rectification or ultraviolet flame detectors for reliable flame presence verification.
Technical Specifications:
- SERIES/FAMILY: R4343D
- COMPONENT TYPE: Primary Flame Safeguard Control
- ELECTRICAL SPECS: 120VAC, 50/60 Hz Input
- CONTROL LOGIC: Intermittent Pilot Operation
- IGNITION TIMING: 15-second Trial For Ignition (TFI)
- FLAME FAILURE RESPONSE TIME: 2.0 seconds maximum
- FLAME SENSOR COMPATIBILITY: Rectification type (e.g., C7012) or Ultraviolet type (e.g., C7027, C7035, C7044)
- MOUNTING: Q7001A Sub-base (sold separately)
- ENVIRONMENTAL/ENCLOSURE: NEMA 1 equivalent for control cabinet installation
- APPLICATION: Commercial and industrial oil or gas burners requiring intermittent pilot ignition and continuous flame supervision