PRODUCT DESCRIPTION
HONEYWELL TC810E1040 - Network Interface Module
This module facilitates high-speed, peer-to-peer communication between multiple fire alarm control panels within a distributed fire protection system. It enables the integration of multiple XLS80/XLS1000 series panels into a unified network, providing system-wide event reporting, control, and status monitoring for large-scale commercial and industrial facilities. Its design ensures robust data integrity and rapid response across the network.
Technical Specifications:
- SERIES/FAMILY: XLS80/XLS1000 Series Fire Alarm Systems
- COMPONENT TYPE: Network Interface Module (NIM)
- ELECTRICAL SPECS: Powered directly from the host Fire Alarm Control Panel, typically 24VDC
- INTERFACE/CONTROL: Proprietary high-speed network protocol for peer-to-peer communication. Supports network wiring via shielded twisted-pair copper or fiber optic cable (requires external fiber optic transceivers).
- NETWORK TOPOLOGY: Supports Class A (Style 7) or Class B (Style 4) network wiring configurations
- FUNCTIONALITY: Enables system-wide event reporting, control command propagation, and status synchronization across networked fire alarm control panels
- ENVIRONMENTAL/MOUNTING: Designed for internal mounting within compatible HONEYWELL Fire Alarm Control Panel enclosures or dedicated network enclosures
- COMPATIBILITY/APPLICATION: Specifically engineered for integration with HONEYWELL XLS80 and XLS1000 series Fire Alarm Control Panels in large-scale, multi-panel fire detection and suppression systems