PRODUCT DESCRIPTION
MITSUBISHI MMP-T32LF 0.63A - Motor Protection Circuit Breaker
The MITSUBISHI MMP-T32LF 0.63A is a thermal-magnetic motor protection circuit breaker designed for the protection of AC motors and other inductive loads. This device integrates overload and short-circuit protection functions, ensuring operational safety and compliance within industrial control systems. It is engineered for direct integration into motor starter combinations and industrial distribution panels, providing reliable circuit interruption and motor safeguarding.
Technical Specifications:
- SERIES/FAMILY: MMP-T Series
- COMPONENT TYPE: Motor Protection Circuit Breaker (MPCB), Thermal-Magnetic Type
- ELECTRICAL SPECS:
- RATED OPERATIONAL CURRENT (Ie): 0.63A (Thermal trip setting range upper limit)
- THERMAL TRIP ADJUSTMENT RANGE: 0.4A to 0.63A
- MAGNETIC TRIP SETTING: Fixed at approximately 13 x Ie (8.19A)
- RATED OPERATIONAL VOLTAGE (Ue): Up to 690VAC
- RATED INSULATION VOLTAGE (Ui): 690V
- RATED IMPULSE WITHSTAND VOLTAGE (Uimp): 6kV
- RATED FREQUENCY: 50/60 Hz
- RATED ULTIMATE SHORT-CIRCUIT BREAKING CAPACITY (Icu): 10kA at 400VAC
- PHASE: 3-Phase (suitable for single-phase applications)
- MECHANICAL/PHYSICAL:
- FRAME SIZE: T32
- OPERATION: Rotary handle with ON/OFF/TRIP indication
- INTERFACE/CONTROL:
- CONTROL: Manual ON/OFF operation
- AUXILIARY CONTACTS: Optional, side-mounted (not included as standard with base unit)
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20 (terminals), IP40 (front panel when installed in enclosure)
- OPERATING TEMPERATURE: -20°C to +60°C
- MOUNTING STYLE: 35mm DIN Rail
- COMPATIBILITY/APPLICATION:
- TARGET SYSTEMS: Protection of AC motors, transformers, and resistive loads
- MACHINE TYPES: Industrial machinery, HVAC systems, pump control, conveyor systems, general industrial control panels