PRODUCT DESCRIPTION
PEPPERL & FUCHS 097967 - KFD2-CD-EX1.32 Isolated Barrier, Current Driver
The PEPPERL & FUCHS 097967 is a KFD2-CD-EX1.32 K-System isolated barrier, engineered for intrinsically safe signal conditioning in hazardous area applications. This single-channel current driver provides galvanic isolation between the safe area control system and field devices located in Zone 0, 1, or 2, ensuring reliable and compliant operation of actuators and positioners. It converts a safe area control signal into an intrinsically safe current output for precise process control.
Technical Specifications:
- SERIES/FAMILY: K-System, KFD2 Series
- COMPONENT TYPE: Isolated Barrier, Current Driver
- ELECTRICAL SPECS:
- POWER SUPPLY: 24 VDC (19.2 VDC to 30 VDC)
- SAFE AREA INPUT: 4-20 mA (current source or active current input)
- HAZARDOUS AREA OUTPUT: Intrinsically Safe 4-20 mA current loop
- ISOLATION: Galvanic isolation between input, output, and power supply
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20
- MOUNTING: 35 mm DIN rail mountable
- OPERATING TEMPERATURE: -20 °C to +60 °C
- HAZARDOUS AREA CERTIFICATION: ATEX, IECEx, FM, cULus for Ex ia IIC, Ex ib IIC
- INTERFACE/CONTROL:
- CHANNELS: 1-channel
- SIGNAL TYPE: Analog current signal conditioning
- COMPATIBILITY/APPLICATION:
- TARGET SYSTEMS: Process control systems (DCS, PLC), Safety Instrumented Systems (SIS)
- FIELD DEVICES: I/P converters, valve positioners, actuators in hazardous locations
- INDUSTRIES: Chemical, Oil & Gas, Pharmaceutical, Food & Beverage, Water/Wastewater