PRODUCT DESCRIPTION
PEPPERL & FUCHS 277761 - KFD2-SR2-EX1.W.SM Safety Relay
The PEPPERL & FUCHS 277761 is a KFD2-SR2-EX1.W.SM safety relay, part of the K-System series, designed for reliable signal processing from hazardous area inputs to safe area control systems. It provides intrinsic safety isolation and switching functions, crucial for implementing Safety Instrumented Systems (SIS) in process automation and machinery safety applications. This module ensures high integrity monitoring and control of safety-related circuits.
Technical Specifications:
- SERIES/FAMILY: K-System, KFD2 Series
- COMPONENT TYPE: Safety Relay / Intrinsically Safe Barrier
- ELECTRICAL SPECS:
- SUPPLY VOLTAGE: 20-35VDC (Nominal 24VDC)
- INPUT: 1-channel, intrinsically safe input for dry contacts or NAMUR sensors from hazardous areas
- OUTPUT: 2 Normally Open (NO) relay contacts, 1 Normally Closed (NC) relay contact
- SWITCHING CAPACITY: Max. 250VAC/DC, 2A (resistive load)
- INTERFACE/CONTROL:
- INPUT SIGNAL: Control circuit from hazardous area (e.g., proximity switch, mechanical switch)
- OUTPUT SIGNAL: Potential-free relay contacts for safe area control
- DIAGNOSTICS: Line fault detection (open/short circuit) for input wiring
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20 (for control cabinet installation)
- MOUNTING: 35mm DIN-rail mountable
- OPERATING TEMPERATURE: -20 °C to +60 °C
- COMPATIBILITY/APPLICATION:
- FUNCTIONAL SAFETY: Certified up to Safety Integrity Level (SIL) 3 according to IEC 61508/61511, and Performance Level (PL) e according to ISO 13849
- HAZARDOUS AREA CERTIFICATION: ATEX, IECEx, FM, cULus for intrinsic safety applications
- TARGET APPLICATIONS: Emergency shutdown systems (ESD), fire and gas (F&G) systems, safety gates, light curtains, process control in chemical, oil & gas, and pharmaceutical industries.