PRODUCT DESCRIPTION
PEPPERL & FUCHS 283011 - K-System Intrinsically Safe Switch Amplifier
This K-System safety relay switch amplifier, identified as KFD2-SR2-EX1.W.SM, provides galvanic isolation and signal conditioning for intrinsically safe circuits in hazardous areas. It is engineered for reliable detection of NAMUR sensors or mechanical contacts, converting these signals into potential-free relay outputs for control systems in non-hazardous zones, ensuring functional safety in process automation applications.
Technical Specifications:
- SERIES/FAMILY: K-System (KFD2-SR2-EX1.W.SM)
- COMPONENT TYPE: Intrinsically Safe Switch Amplifier / Safety Relay
- ELECTRICAL SPECS: 20-35V DC Supply Voltage (24V DC nominal), Max 1.5W Power Consumption, 2 x Normally Open (NO) Relay Outputs, 1 x Normally Closed (NC) Fault Relay Output, 250V AC/DC 2A Switching Capacity per output
- MECHANICAL/PHYSICAL: Compact DIN rail mountable module, Screw terminals
- INTERFACE/CONTROL: 2-channel intrinsically safe input for NAMUR sensors (EN 60947-5-6) or dry contacts, Potential-free relay outputs, Line fault detection (wire break, short circuit) for input circuits, Configurable via DIP switches for operating mode and diagnostics
- ENVIRONMENTAL/MOUNTING: IP20 (terminals) / IP40 (housing) Protection, 35 mm DIN rail mounting, -20 °C to +60 °C Operating Temperature, Certified for hazardous areas (e.g., ATEX, IECEx, cULus for Ex ia IIC T4 Ga/Gb)
- COMPATIBILITY/APPLICATION: Suitable for functional safety applications up to SIL 2 (IEC 61508), Integrates NAMUR proximity switches, limit switches, and emergency stop buttons from hazardous areas with control systems in safe areas, Utilized in chemical, petrochemical, oil & gas, and pharmaceutical industries