PEPPERL & FUCHS 301134 - K-System Intrinsic Safety Barrier, Switch Repeater
This intrinsic safety barrier from the K-System family provides galvanic isolation and signal conditioning for two independent channels, enabling the safe operation of NAMUR proximity sensors or mechanical contacts located in hazardous areas. It converts input signals into isolated relay outputs for control systems in the safe area, incorporating line fault detection for enhanced system integrity. Engineered for process automation applications requiring SIL 2 functional safety.
Technical Specifications:
- SERIES/FAMILY: K-System (KFD2)
- COMPONENT TYPE: Intrinsic Safety Barrier, Switch Repeater
- CHANNELS: Two (2) independent channels
- ELECTRICAL SPECS:
- NOMINAL SUPPLY VOLTAGE: 24 VDC
- INPUT TYPE: NAMUR proximity sensors or mechanical contacts
- OUTPUT TYPE: Relay, changeover contact (SPDT)
- SWITCHING FREQUENCY: 0 to 5 kHz
- SAFETY PARAMETERS:
- HAZARDOUS AREA CLASSIFICATION: Ex ia IIC (for connected field devices)
- FUNCTIONAL SAFETY: Up to SIL 2 (IEC 61508)
- INTERFACE/CONTROL:
- SIGNAL CONDITIONING: Converts NAMUR/contact signals to relay outputs
- FAULT DETECTION: Line fault detection (LFD) for open and short circuits
- ENVIRONMENTAL/MOUNTING:
- ENCLOSURE RATING: IP20
- MOUNTING: 35 mm DIN rail
- OPERATING TEMPERATURE: -20 to +60 degrees Celsius
- COMPATIBILITY/APPLICATION:
- TARGET SYSTEMS: PLCs, DCS, and other safe area control systems
- APPLICATIONS: Process control in chemical, oil & gas, pharmaceutical industries
- FIELD DEVICES: Compatible with NAMUR sensors and dry contacts in Zone 0, 1, 2 hazardous areas