The product is an item that has never been used and has been sourced from an excess supplier.
Never used in a production environment, but it may have been powered on for testing.
The product may show slight superficial signs of handling, but no signs of use or damage.
It may or may not have the original packaging. If the original packaging is not available, the product will generally be packaged in aftermarket packaging or branded BAS.
Hardware, accessories, or instructions present in the factory new version of the product may be missing. The manufacturer's warranty may not apply.
The product may have older date or serial codes compared to those available directly from the manufacturer or authorized retailers.
Products may vary by country of origin and by language used on the packaging.
The packaging may contain markings not from the original manufacturer (OEM).
This K-System safety relay switch amplifier provides intrinsic safety isolation and signal conditioning for two-channel applications in hazardous areas. It is engineered for monitoring NAMUR sensors or mechanical contacts, delivering reliable switching outputs for safety instrumented systems. The module integrates line fault detection and is certified for use in safety applications up to SIL 2 and PL c.
Technical Specifications:
SERIES/FAMILY: K-System, KFD2-SR2-EX1.W.SM
COMPONENT TYPE: Switch Amplifier / Safety Relay
ELECTRICAL SPECS:
SUPPLY VOLTAGE: 20-35V DC (24V DC nominal)
POWER CONSUMPTION: 1.5W at 24V DC
INPUT: 2-channel for NAMUR sensors (EN 60947-5-6) or dry contacts
INPUT SIGNAL: NAMUR proximity switch or potential-free contact
OUTPUT SIGNAL: Potential-free relay contact
FUNCTIONALITY: Line fault detection (open/short circuit) for input lines
OPERATING MODE: Configurable for normally open or normally closed input logic
ENVIRONMENTAL/MOUNTING:
IP RATING: IP20
OPERATING TEMPERATURE: -20 to +60 °C (-4 to +140 °F)
MOUNTING: 35mm DIN rail
HAZARDOUS AREA CERTIFICATION: ATEX, IECEx for Zone 2 (Ex nA [ia Ga] IIC T4 Gc)
COMPATIBILITY/APPLICATION:
SAFETY INTEGRITY LEVEL (SIL): Up to SIL 2 (IEC 61508)
PERFORMANCE LEVEL (PL): Up to PL c (EN ISO 13849-1)
TARGET APPLICATIONS: Emergency shutdown (ESD) systems, fire and gas (F&G) systems, process control in hazardous environments, safety-related sensor monitoring.
Every BAS partner is entitled to highly personalized support.
Joining the network of partners and distributors of the BAS group means becoming part of our ecosystem, embracing our vision and our mission. All of this is done by implementing our "just in time" business model and our strategy of proximity to the end customer to offer professionalism, speed, and quality to the clients who refer to our company on a daily basis.
SERVICE PARTNER
Join a network of assistancethat
is always efficient and reliable.
News, updates, and offers dedicated to your needs.
Please note that Automation Service is an independent laboratory operating autonomously and is not part of the sales network of the manufacturers whose brands it services.