PRODUCT DESCRIPTION
PEPPERL & FUCHS 324831 - K-System PROFINET Isolated Barrier
This K-System isolated barrier functions as a PROFINET gateway, providing intrinsic safety and galvanic isolation for a single channel of hazardous area signals. It converts intrinsically safe current or digital inputs from Zone 0/1/2 into PROFINET IO data for integration into safe area control systems, ensuring reliable and compliant signal transmission in process automation environments.
Technical Specifications:
- SERIES/FAMILY: K-System (KFD2)
- COMPONENT TYPE: Isolated Barrier, PROFINET Gateway, Signal Conditioner
- ELECTRICAL SPECS: 20-35VDC Supply Voltage (Nominal 24VDC)
- INPUT CHANNELS: 1-channel, Intrinsically Safe
- INPUT SIGNAL TYPE: Configurable for 4-20mA Current Input or Digital Switch/Proximity Sensor Input
- OUTPUT PROTOCOL: PROFINET IO (Real-Time and Isochronous Real-Time capable)
- HAZARDOUS AREA CLASSIFICATION: Ex ia/ib IIC/IIB/IIA (for input circuit)
- INTERFACE/CONTROL: PROFINET IO communication via RJ45 ports, GSDML file configuration
- ENVIRONMENTAL/MOUNTING: IP20 Protection, 35mm DIN Rail Mounting
- OPERATING TEMPERATURE: -20°C to +60°C
- COMPATIBILITY/APPLICATION: Integration of hazardous area field devices into PROFINET-based Distributed Control Systems (DCS) and Programmable Logic Controllers (PLC)