PRODUCT DESCRIPTION
PEPPERL & FUCHS 421280 - KFD2-SR2-EX1.W.SM Isolated Barrier with Safety Relay Output
This intrinsically safe isolated barrier from the K-System series is engineered for reliable signal transmission between hazardous and safe areas. It provides two independent channels for connecting NAMUR proximity sensors or mechanical contacts in Zone 0, 1, or 2, and outputs two potential-free relay contacts to the safe area. The module integrates line fault detection and is suitable for safety instrumented systems requiring SIL 2 compliance.
Technical Specifications:
- SERIES/FAMILY: K-System, KFD2 Series
- COMPONENT TYPE: Isolated Barrier with Safety Relay Output (2-channel switch amplifier)
- ELECTRICAL SPECS:
- SUPPLY VOLTAGE: 20-35 VDC (wide range)
- INPUT: Intrinsically safe input for NAMUR sensors or potential-free contacts
- OUTPUT: 2 x Normally Open (NO) potential-free relay contacts
- RELAY CONTACT RATING: 250 VAC / 2 A or 30 VDC / 2 A (resistive load)
- INTERFACE/CONTROL:
- INPUT SIGNAL: NAMUR (EN 60947-5-6) or dry contact
- OUTPUT SIGNAL: Discrete relay contact
- DIAGNOSTICS: Line fault detection (wire break, short circuit)
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20
- MOUNTING STYLE: 35 mm DIN rail
- OPERATING TEMPERATURE: -20 °C to +60 °C
- COMPATIBILITY/APPLICATION:
- HAZARDOUS AREA CLASSIFICATION: Zone 0, 1, 2 (gas) Zone 20, 21, 22 (dust)
- SAFETY INTEGRITY LEVEL: Up to SIL 2 (IEC 61508/61511)
- TARGET SYSTEMS: Process control systems, Emergency Shutdown (ESD) systems, Fire & Gas (F&G) systems, PLCs
- FUNCTION: Intrinsic safety isolation, signal conditioning, safety interlocking