PRODUCT DESCRIPTION
PEPPERL & FUCHS 456526 - Intrinsic Safety Barrier - Switch Amplifier
This device is a dual-channel intrinsic safety barrier from the K-System KFD2 series, engineered for reliable signal conditioning and galvanic isolation between hazardous and safe areas. It facilitates the operation of NAMUR proximity sensors or mechanical contacts located in explosive atmospheres, providing isolated relay outputs for control systems. Designed for critical process automation applications, it ensures compliance with international intrinsic safety standards.
Technical Specifications:
- SERIES/FAMILY: K-System, KFD2-SR2-Ex1.W
- COMPONENT TYPE: Intrinsic Safety Barrier, 2-Channel Switch Amplifier
- ELECTRICAL SPECS:
- SUPPLY VOLTAGE: 20-35V DC (via power rail or terminals)
- POWER CONSUMPTION: < 1.5W at 24V DC
- INPUT: 2 channels for NAMUR sensors (EN 60947-5-6) or dry contacts
- OUTPUT: 2 isolated relay outputs, SPDT (changeover contact)
- SWITCHING CAPACITY: Max. 250VAC/2A or 125VDC/2A (resistive load)
- INTERFACE/CONTROL:
- SIGNAL TYPE: Digital input from hazardous area, relay output to safe area
- FAULT DETECTION: Line fault detection (LFD) for open and short circuits
- INDICATORS: LEDs for power, switching status, and fault conditions
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20
- MOUNTING: 35mm DIN rail mount
- OPERATING TEMPERATURE: -20 to +60 °C (-4 to +140 °F)
- HAZARDOUS AREA APPROVALS: ATEX, IECEx, FM, cULus for Zone 0, 1, 2 applications
- COMPATIBILITY/APPLICATION:
- SENSOR COMPATIBILITY: NAMUR proximity sensors, mechanical switches
- TARGET SYSTEMS: Distributed Control Systems (DCS), Programmable Logic Controllers (PLC), Safety Instrumented Systems (SIS)
- INDUSTRY APPLICATIONS: Chemical, Oil & Gas, Pharmaceutical, Power Generation, Water/Wastewater Treatment
- SAFETY INTEGRITY: Suitable for applications up to SIL2 (IEC 61508)