PRODUCT DESCRIPTION
PEPPERL & FUCHS 800182 - K-System Isolated Barrier Solenoid Driver
This K-System isolated barrier provides intrinsic safety for controlling solenoid valves, alarms, or LEDs located in hazardous areas. It features galvanic isolation between the control input, intrinsically safe output, and power supply, ensuring reliable and safe operation in process automation applications requiring compliance with international hazardous area standards.
Technical Specifications:
- SERIES/FAMILY: K-System (KFD2)
- COMPONENT TYPE: Isolated Barrier, Solenoid Driver
- ELECTRICAL SPECS:
- SUPPLY VOLTAGE: 20-35VDC via Power Rail or Terminals
- INPUT: Digital Input, 24VDC Nominal (from safe area control system)
- OUTPUT: Intrinsically Safe Switching Output, Current Limited (for hazardous area load)
- OUTPUT CURRENT: Up to 50mA (typical for low power applications)
- POWER DISSIPATION: < 1.5W
- INTERFACE/CONTROL:
- SIGNAL TYPE: Digital ON/OFF
- ISOLATION: Galvanic Isolation (Input/Output/Power Supply)
- FAULT DETECTION: Line Fault Detection (Open/Short Circuit) for field circuit
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20
- MOUNTING: 35mm DIN Rail
- OPERATING TEMPERATURE: -20 to +60 °C
- HAZARDOUS AREA CERTIFICATION: ATEX, IECEx, FM, cULus (for Zone 0, 1, 2 / Class I, II, III, Div 1, 2)
- COMPATIBILITY/APPLICATION:
- TARGET LOAD: Solenoid Valves, Alarms, LEDs in hazardous areas
- SYSTEM INTEGRATION: PLC, DCS, ESD systems
- INDUSTRY: Chemical, Oil & Gas, Pharmaceutical, Food & Beverage, Water/Wastewater Treatment