PRODUCT DESCRIPTION
SCHNEIDER ELECTRIC 33799 - 3-Pole Contactor
This device is a SCHNEIDER ELECTRIC TeSys D series 3-pole contactor, specifically model LC1D09M7, designed for robust switching of inductive and resistive loads in industrial control applications. It features a 220-230VAC 50/60Hz control coil and integrates one normally open (NO) and one normally closed (NC) auxiliary contact for signaling and interlocking functions. Primary applications include motor control, heating element switching, and general power circuit management within automation panels.
Technical Specifications:
- SERIES/FAMILY: TeSys D
- COMPONENT TYPE: Contactor
- ELECTRICAL SPECS:
- RATED OPERATIONAL CURRENT (AC-3): 9A at <= 440V
- RATED OPERATIONAL CURRENT (AC-1): 25A at <= 690V
- COIL VOLTAGE: 220-230VAC 50/60Hz
- NUMBER OF POLES: 3P
- POWER RATING (AC-3): 2.2 kW at 220-230V, 4 kW at 380-400V, 5.5 kW at 415-690V
- RATED INSULATION VOLTAGE (UI): 690V (power circuit), 600V (signaling circuit)
- RATED IMPULSE WITHSTAND VOLTAGE (UIMP): 6kV
- OPERATIONAL FREQUENCY: 50/60Hz
- MECHANICAL/PHYSICAL:
- AUXILIARY CONTACTS: 1 NO + 1 NC
- MOUNTING: 35mm DIN rail or screw fixing
- MECHANICAL ENDURANCE: 15 Mcycles
- ELECTRICAL ENDURANCE: 1.6 Mcycles (AC-3 at 9A)
- TERMINALS: Screw clamp
- INTERFACE/CONTROL:
- CONTROL TYPE: AC Electromagnet
- FEEDBACK: Integrated auxiliary contacts for status indication
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20 (terminals), IP65 (front face with optional cover)
- OPERATING TEMPERATURE: -5 to 60 degrees C
- STORAGE TEMPERATURE: -60 to 80 degrees C
- ALTITUDE: 0-3000m without derating
- COOLING METHOD: Natural convection
- COMPATIBILITY/APPLICATION: Motor control systems, resistive load switching, HVAC equipment, pumping stations, industrial machinery, and general automation panels.