PRODUCT DESCRIPTION
SCHNEIDER ELECTRIC LRD08C - Thermal Overload Relay
The SCHNEIDER ELECTRIC LRD08C is a TeSys LRD thermal overload relay engineered for robust motor protection in industrial control systems. It provides reliable safeguarding against overloads, phase failure, and prolonged starting conditions for 3-phase AC motors, integrating directly with TeSys D contactors. This device ensures operational continuity and equipment longevity in applications requiring precise current monitoring and fault detection.
Technical Specifications:
- SERIES/FAMILY: TeSys LRD
- COMPONENT TYPE: Thermal Overload Relay
- ELECTRICAL SPECS:
- OPERATIONAL CURRENT RANGE: 2.5 - 4 A
- RATED OPERATIONAL VOLTAGE (Ue): Up to 690 VAC 50/60 Hz
- RATED INSULATION VOLTAGE (Ui): 690 VAC
- RATED IMPULSE WITHSTAND VOLTAGE (Uimp): 6 kV
- PHASE: 3-Phase
- TRIP CLASS: Class 10A
- MECHANICAL/PHYSICAL:
- RESET FUNCTION: Manual and Automatic
- AUXILIARY CONTACTS: 1 Normally Open (NO) + 1 Normally Closed (NC)
- INTERFACE/CONTROL:
- CONNECTION TYPE: Screw Clamp Terminals
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20 (Terminals), IP40 (Casing)
- OPERATING TEMPERATURE: -20 to 60 degrees Celsius
- MOUNTING STYLE: Direct mounting under TeSys D contactors (e.g., LC1D09-D38) or standalone with adapter block (e.g., LAD7B106) for DIN rail/plate mounting
- COMPATIBILITY/APPLICATION:
- TARGET SYSTEMS: Industrial motor control circuits
- PROTECTION FUNCTION: Overload protection, phase failure protection
- COMPATIBLE CONTACTORS: TeSys D series (LC1D09, LC1D12, LC1D18, LC1D25, LC1D32, LC1D38)