PRODUCT DESCRIPTION
SCHNEIDER ELECTRIC LV846314 - Air Circuit Breaker
The SCHNEIDER ELECTRIC LV846314 is a MasterPact MTZ2 series low voltage air circuit breaker engineered for primary circuit protection and power distribution within industrial and commercial electrical installations. It integrates advanced Micrologic X trip unit technology for precise overcurrent, short-circuit, and ground fault protection, facilitating energy management and system reliability in critical power infrastructure, data centers, and heavy industrial applications. This component is designed for integration into switchgear assemblies requiring high breaking capacity and selective coordination.
Technical Specifications:
- SERIES/FAMILY: MasterPact MTZ2
- COMPONENT TYPE: Air Circuit Breaker (ACB)
- ELECTRICAL SPECS:
- NOMINAL CURRENT (In): 6300A
- RATED OPERATIONAL VOLTAGE (Ue): 690VAC
- POLES: 4P
- BREAKING CAPACITY (Icu at 400/415VAC): 100kA (H1 class)
- SERVICE BREAKING CAPACITY (Ics at 400/415VAC): 100kA (H1 class)
- RATED IMPULSE WITHSTAND VOLTAGE (Uimp): 12kV
- RATED INSULATION VOLTAGE (Ui): 1000V
- FREQUENCY: 50/60 Hz
- MECHANICAL/PHYSICAL:
- FRAME SIZE: MTZ2 4000A frame
- MOUNTING TYPE: Drawout
- OPERATION: Electrical (motorized charging) or Manual
- INTERFACE/CONTROL:
- TRIP UNIT: Micrologic X series (configurable for L, S, I, G, N protection)
- PROTECTION FUNCTIONS: Long-time (Overload), Short-time, Instantaneous, Ground Fault, Neutral Protection
- COMMUNICATION: Modbus, Ethernet/IP, PROFINET (via optional communication modules)
- FEEDBACK: Auxiliary contacts for status indication, trip indication
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP30 (front face with door)
- COOLING METHOD: Natural convection
- MOUNTING STYLE: Panel-mounted (vertical or horizontal orientation)
- OPERATING TEMPERATURE: -25 to 70 degrees C
- COMPATIBILITY/APPLICATION:
- APPLICATIONS: Main incoming circuit protection, sub-distribution, generator protection, motor protection, and critical power system management in industrial plants, data centers, hospitals, and commercial buildings.
- STANDARDS: IEC 60947-2