PRODUCT DESCRIPTION
SCHNEIDER ELECTRIC LV847432 - Molded Case Circuit Breaker with Earth Leakage Protection
SCHNEIDER ELECTRIC LV847432 is a ComPact NSXm series Molded Case Circuit Breaker (MCCB) engineered for robust overcurrent, short-circuit, and earth leakage protection in low voltage electrical distribution systems. This 4-pole, 160A device integrates an electronic MicroLogic 4.2 Vigi trip unit, providing precise fault discrimination and adjustable protection parameters. It is designed for critical industrial and commercial applications requiring reliable circuit isolation and enhanced safety.
Technical Specifications:
- SERIES/FAMILY: ComPact NSXm
- COMPONENT TYPE: Molded Case Circuit Breaker (MCCB) with Integrated Earth Leakage Protection
- ELECTRICAL SPECS:
- NOMINAL CURRENT (In): 160A
- NUMBER OF POLES: 4P
- BREAKING CAPACITY (Icu): 36kA at 400/415VAC (N Category)
- RATED OPERATIONAL VOLTAGE (Ue): 690VAC
- TRIP UNIT TYPE: MicroLogic 4.2 Vigi Electronic Trip Unit
- PROTECTION FUNCTIONS: Long-time (overload), Short-time, Instantaneous (short-circuit), Earth Leakage (Vigi)
- EARTH LEAKAGE SENSITIVITY (IΔn): Adjustable from 0.03A to 30A
- EARTH LEAKAGE TIME DELAY (Δt): Adjustable from instantaneous to 4s
- MECHANICAL/PHYSICAL:
- FRAME SIZE: NSXm 160
- MOUNTING TYPE: Fixed, suitable for DIN rail or plate mounting
- CONNECTION TYPE: Front terminals
- INTERFACE/CONTROL:
- LOCAL INDICATION: Trip indication, Earth leakage indication, Load level LEDs
- ADJUSTMENTS: Front-face rotary switches for trip unit settings (Ir, tr, Isd, tsd, Ii, IΔn, Δt)
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP40 (front face with escutcheon)
- COOLING METHOD: Natural convection
- OPERATING TEMPERATURE RANGE: -25°C to +70°C
- STORAGE TEMPERATURE RANGE: -50°C to +85°C
- COMPATIBILITY/APPLICATION:
- PRIMARY APPLICATION: Low voltage electrical distribution networks
- PROTECTION TARGETS: Feeders, motors, generators, and critical loads
- STANDARDS COMPLIANCE: IEC 60947-2, IEC 60947-5-1, IEC 60364