PRODUCT DESCRIPTION
SCHNEIDER ELECTRIC LV848427 - Air Circuit Breaker Fixed Part
This component is a MasterPact MTZ2 series fixed-type air circuit breaker frame, engineered for robust low voltage power distribution and protection applications. It serves as the foundational element for electrical installations requiring high breaking capacity and reliable overcurrent protection. The unit is designed for integration with advanced Micrologic X control units, enabling comprehensive monitoring, control, and communication capabilities within industrial power management systems.
Technical Specifications:
- SERIES/FAMILY: MasterPact MTZ2
- COMPONENT TYPE: Air Circuit Breaker Fixed Part
- ELECTRICAL SPECS:
- RATED FRAME CURRENT: 2000A
- RATED OPERATIONAL VOLTAGE (Ue): 690VAC (maximum)
- RATED INSULATION VOLTAGE (Ui): 1000V
- RATED IMPULSE WITHSTAND VOLTAGE (Uimp): 12kV
- BREAKING CAPACITY (Icu at 400/415VAC): 65kA (H1 level)
- POLES: 3P
- FREQUENCY: 50/60Hz
- MECHANICAL/PHYSICAL:
- FRAME SIZE: MTZ2 20 (2000A frame)
- MOUNTING TYPE: Fixed
- CONNECTION TYPE: Front connection (standard for fixed type)
- INTERFACE/CONTROL:
- CONTROL UNIT COMPATIBILITY: Designed for integration with Micrologic X series control units (e.g., 2.0 X, 5.0 X, 6.0 X, 7.0 X)
- COMMUNICATION CAPABILITY: Supports Modbus, Ethernet, and other protocols via optional communication modules when equipped with a Micrologic X control unit
- AUXILIARY CONTACTS: Configurable via optional modules
- ENVIRONMENTAL/MOUNTING:
- COOLING METHOD: Natural air convection
- OPERATING TEMPERATURE: -25 to 70 degrees C (with derating above 40 degrees C)
- STORAGE TEMPERATURE: -50 to 85 degrees C
- MOUNTING POSITION: Vertical or horizontal
- COMPATIBILITY/APPLICATION:
- TARGET SYSTEMS: Low voltage power distribution networks, main incoming and outgoing feeders, generator protection, motor protection, transformer protection
- MACHINE TYPES: Industrial plants, commercial buildings, data centers, infrastructure projects