SCHNEIDER ELECTRIC LV850064SP - Air Circuit Breaker
This device is a MasterPact MTZ2 series 3-pole fixed air circuit breaker, engineered for primary power distribution and protection in industrial and commercial low voltage switchboards. It integrates an advanced Micrologic X electronic trip unit for precise overcurrent, short-circuit, and ground fault protection, ensuring system reliability and operational continuity. Designed for high-current applications, it facilitates robust electrical infrastructure management and comprehensive system diagnostics.
Technical Specifications:
- SERIES/FAMILY: MasterPact MTZ2
- COMPONENT TYPE: Air Circuit Breaker (ACB)
- ELECTRICAL SPECS:
- NOMINAL CURRENT (In): 6400 A
- POLES: 3-Pole
- RATED OPERATIONAL VOLTAGE (Ue): 690 VAC
- RATED INSULATION VOLTAGE (Ui): 1000 VAC
- RATED IMPULSE WITHSTAND VOLTAGE (Uimp): 12 kV
- RATED SHORT-CIRCUIT BREAKING CAPACITY (Icu): 100 kA at 400/415 VAC
- FREQUENCY: 50/60 Hz
- MECHANICAL/PHYSICAL:
- MOUNTING TYPE: Fixed
- FRAME SIZE: MTZ2 (High current frame)
- OPERATION: Manual or Motorized (configuration dependent)
- INTERFACE/CONTROL:
- PROTECTION UNIT: Integrated Micrologic X Electronic Trip Unit
- PROTECTION FUNCTIONS: Long-time, Short-time, Instantaneous, Ground Fault, Neutral Protection
- COMMUNICATION: Modbus, Ethernet (via optional communication modules)
- MEASUREMENT: Current, Voltage, Power, Energy, Harmonics
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP40 (front face), IP30 (overall)
- COOLING METHOD: Natural Convection
- MOUNTING STYLE: Panel Mounted (Fixed in switchboard)
- OPERATING TEMPERATURE: -25 to 70 degrees C
- COMPATIBILITY/APPLICATION:
- TARGET SYSTEMS: Main Low Voltage Distribution Switchboards, Generator Paralleling Systems, Industrial Power Plants, Data Centers
- APPLICATION: Primary circuit protection, selective coordination, power quality monitoring, energy management