PRODUCT DESCRIPTION
SCHNEIDER ELECTRIC LVS08275 - Molded Case Circuit Breaker
The SCHNEIDER ELECTRIC LVS08275 is a ComPact NSXm series molded case circuit breaker engineered for industrial low-voltage power distribution and protection applications. This device features a 3-pole, 80A frame equipped with a fixed magnetic-only (MA) trip unit, providing instantaneous short-circuit protection for circuits, motors, and feeders. It is designed for integration into switchboards and control panels, ensuring compliance with IEC 60947-2 standards for circuit protection.
Technical Specifications:
- SERIES/FAMILY: ComPact NSXm
- COMPONENT TYPE: Molded Case Circuit Breaker (MCCB)
- ELECTRICAL SPECS:
- NOMINAL CURRENT: 80A
- NUMBER OF POLES: 3P (3 Poles)
- PROTECTED POLES: 3D (3 Protected Poles)
- TRIP UNIT TYPE: MA (Magnetic Only)
- NOMINAL OPERATIONAL VOLTAGE (Ue): Up to 690VAC
- NOMINAL INSULATION VOLTAGE (Ui): 800V
- NOMINAL IMPULSE WITHSTAND VOLTAGE (Uimp): 8kV
- FREQUENCY: 50/60 Hz
- NOMINAL SERVICE BREAKING CAPACITY (Ics): 100% of Icu
- NOMINAL ULTIMATE BREAKING CAPACITY (Icu): 36kA at 400/415VAC (N-type performance)
- MECHANICAL/PHYSICAL:
- FRAME SIZE: NSXm 80
- TRIP UNIT ADJUSTMENT: Fixed magnetic threshold
- MOUNTING TYPE: Fixed, front connection or rear connection
- INTERFACE/CONTROL:
- TRIP UNIT TECHNOLOGY: Magnetic Only
- INDICATORS: Trip indication, ON/OFF position
- AUXILIARIES: Compatible with optional auxiliary contacts, shunt trips, undervoltage releases
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP40 (front face with door) / IP20 (terminals)
- OPERATING TEMPERATURE: -25 to 70 degrees C
- STORAGE TEMPERATURE: -50 to 85 degrees C
- POLLUTION DEGREE: 3
- MOUNTING POSITION: Vertical or horizontal
- COMPATIBILITY/APPLICATION:
- APPLICATIONS: Industrial power distribution, motor protection, generator protection, feeder protection, branch circuit protection
- STANDARDS: IEC 60947-2