DESCRIPTION DU PRODUIT
SCHNEIDER ELECTRIC ZCE21 - Fixed Plug-in Body for Limit Switch
The SCHNEIDER ELECTRIC ZCE21 is a fixed plug-in body component for the OsiSense XC Standard series of industrial limit switches. It provides a 1 normally open (NO) and 1 normally closed (NC) snap action contact configuration, designed for precise position detection and end-of-travel signaling in automated systems. This contact block integrates into modular limit switch assemblies, facilitating direct control circuit integration across diverse industrial automation applications.
Technical Specifications:
- SERIES/FAMILY: OsiSense XC Standard
- COMPONENT TYPE: Fixed Plug-in Body for Limit Switch (Contact Block)
- ELECTRICAL SPECS:
- CONTACT CONFIGURATION: 1 Normally Open (NO) + 1 Normally Closed (NC)
- CONTACT OPERATION: Snap Action
- RATED INSULATION VOLTAGE (Ui): 500V (IEC), 600V (UL/CSA)
- RATED IMPULSE WITHSTAND VOLTAGE (Uimp): 6 kV
- CONVENTIONAL ENCLOSED THERMAL CURRENT (Ith): 10 A
- RATED OPERATIONAL CURRENT (Ie): AC-15: 3A @ 240V, 1.5A @ 400V DC-13: 0.27A @ 250V
- MINIMUM SWITCHING CURRENT: 5 mA
- MINIMUM SWITCHING VOLTAGE: 5 V
- MECHANICAL/PHYSICAL:
- FORM FACTOR: Modular plug-in contact block
- TERMINATION: Screw clamp terminals
- CABLE CAPACITY: 1 x 0.34...2 x 1.5 mm² (flexible with or without cable end)
- INTERFACE/CONTROL:
- SIGNALING: Direct electrical contact closure/opening
- FEEDBACK: Binary (ON/OFF)
- ENVIRONMENTAL/MOUNTING:
- OPERATING TEMPERATURE: -25 to 70 °C
- STORAGE TEMPERATURE: -40 to 70 °C
- MOUNTING: Plug-in to ZCKD series limit switch heads
- COMPATIBILITY/APPLICATION:
- COMPATIBLE HEADS: SCHNEIDER ELECTRIC OsiSense XC Standard ZCKD series
- TYPICAL APPLICATIONS: Position sensing, presence detection, end-of-travel detection, safety interlocks in industrial machinery, conveyors, material handling systems