OPIS PRODUKTU
SCHNEIDER ELECTRIC A9L16298 - Residual Current Circuit Breaker with Overcurrent Protection (RCBO)
The SCHNEIDER ELECTRIC A9L16298 is a modular Acti 9 iDPN Vigi series device engineered for comprehensive electrical circuit protection. This component integrates overcurrent protection against both overload and short-circuit conditions with residual current protection against earth leakage faults. It is designed for deployment in low-voltage distribution panels within residential, commercial, and light industrial environments, ensuring compliance with critical safety standards for personnel and equipment.
Technical Specifications:
- SERIES/FAMILY: Acti 9 iDPN Vigi
- COMPONENT TYPE: Residual Current Circuit Breaker with Overcurrent Protection (RCBO)
- ELECTRICAL SPECS:
- NOMINAL VOLTAGE: 230VAC
- NOMINAL CURRENT: 16A
- POLES: 1P+N (1 protected pole + switched neutral)
- FREQUENCY: 50/60 Hz
- TRIP CURVE: C (Instantaneous trip between 5 and 10 times nominal current)
- BREAKING CAPACITY: 6kA at 230VAC (IEC/EN 61009-1)
- RESIDUAL CURRENT SENSITIVITY: 30mA
- RESIDUAL CURRENT TYPE: Type A (Detects AC and pulsating DC residual currents)
- MECHANICAL/PHYSICAL:
- FORM FACTOR: Modular DIN rail device
- MODULE WIDTH: 2 modules (36mm)
- INTERFACE/CONTROL:
- INDICATORS: Mechanical fault indicator (red flag for residual current trip, white flag for overcurrent trip)
- CONTROL: Manual toggle for ON/OFF operation, Test button for RCD function verification
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20 (terminals), IP40 (front face when installed in enclosure)
- MOUNTING STYLE: DIN rail (EN 60715)
- OPERATING TEMPERATURE: -25°C to +60°C
- COMPATIBILITY/APPLICATION:
- APPLICATIONS: Protection of final circuits in residential, commercial, and light industrial installations against short-circuits, overloads, and earth leakage currents. Suitable for circuits with AC and pulsating DC components.
- STANDARDS: Conforms to IEC/EN 61009-1