OPIS PRODUKTU
SCHNEIDER ELECTRIC PM 5110 - Digital Power Meter
The SCHNEIDER ELECTRIC PM 5110 is a PowerLogic series power meter engineered for accurate acquisition of electrical parameters in low voltage distribution systems. This device facilitates energy consumption monitoring, demand management, and fundamental power quality assessment, integrating into supervisory control systems via serial communication protocols. It is suitable for sub-billing, cost allocation, and energy efficiency initiatives across industrial, commercial, and infrastructure applications.
Technical Specifications:
- SERIES/FAMILY: PowerLogic PM5000 Series
- COMPONENT TYPE: Digital Power Meter
- ELECTRICAL SPECS:
- NOMINAL VOLTAGE INPUT: Up to 480V AC L-L / 277V AC L-N (direct connection)
- NOMINAL CURRENT INPUT: Via Current Transformers (CTs), 1A or 5A secondary
- MEASUREMENT PARAMETERS: Voltage (L-L, L-N), Current, Frequency, Active Power (kW), Reactive Power (kVAr), Apparent Power (kVA), Power Factor, Active Energy (kWh), Reactive Energy (kVArh), Apparent Energy (kVAh)
- ACCURACY CLASS: 0.5S for Active Energy (IEC 62053-22)
- AUXILIARY POWER SUPPLY: 100-277V AC/DC
- MECHANICAL/PHYSICAL:
- FORM FACTOR: Panel Mount
- DISPLAY: Backlit LCD
- INTERFACE/CONTROL:
- COMMUNICATION PROTOCOL: Modbus RTU (RS-485)
- DIGITAL INPUTS: 2 (for status monitoring or tariff switching)
- DIGITAL OUTPUTS: 2 (for pulse output or alarm indication)
- ENVIRONMENTAL/MOUNTING:
- IP RATING (FRONT FACE): IP52
- MOUNTING STYLE: Panel flush mount, 96x96mm DIN cutout
- OPERATING TEMPERATURE: -10 to 60 degrees Celsius
- COMPATIBILITY/APPLICATION:
- TARGET SYSTEMS: Energy Management Systems (EMS), Building Management Systems (BMS), SCADA systems
- APPLICATION: Sub-billing, cost allocation, energy efficiency monitoring, demand management, basic power quality analysis in industrial, commercial, and infrastructure facilities.