OPIS PRODUKTU
SCHNEIDER ELECTRIC GV2ME326 - Motor Circuit Breaker
The SCHNEIDER ELECTRIC GV2ME326 is a TeSys GV2ME series thermal-magnetic motor circuit breaker designed for the protection and control of three-phase AC motors. It provides comprehensive overload and short-circuit protection, integrating disconnect, control, and protection functions into a single compact unit. This component is engineered for integration into industrial control panels, machinery, and systems requiring robust motor protection, including HVAC, pumping, and conveyor applications.
Technical Specifications:
- SERIES/FAMILY: TeSys GV2ME
- COMPONENT TYPE: Thermal-Magnetic Motor Circuit Breaker
- ELECTRICAL SPECS:
- NOMINAL CURRENT RANGE: 24-32 A
- THERMAL TRIP ADJUSTMENT RANGE: 24-32 A
- MAGNETIC TRIP CURRENT: 13 x In (approximately 416 A at 32A setting)
- RATED OPERATIONAL VOLTAGE (Ue): Up to 690 V AC
- RATED INSULATION VOLTAGE (Ui): 690 V AC
- RATED IMPULSE WITHSTAND VOLTAGE (Uimp): 6 kV
- NUMBER OF POLES: 3P
- TYPICAL MOTOR POWER (400V AC): 15 kW
- BREAKING CAPACITY (Icu): 100 kA at 230/240 V AC, 10 kA at 400/415 V AC
- MECHANICAL/PHYSICAL:
- CONTROL TYPE: Rotary Knob
- MOUNTING: 35 mm DIN Rail or Screw Fixing
- TERMINALS: Screw Clamp Terminals
- INTERFACE/CONTROL:
- PROTECTION FUNCTIONS: Overload, Short-Circuit
- AUXILIARY CONTACTS: Optional (via add-on blocks)
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20 (Terminal Block), IP40 (Front Face with enclosure)
- OPERATING TEMPERATURE: -20 to 60 °C
- POLLUTION DEGREE: 3
- COMPATIBILITY/APPLICATION:
- APPLICATIONS: Motor protection and control in industrial control panels, machinery, HVAC systems, pumping stations, conveyors, and general industrial automation.
- STANDARDS: IEC 60947-2, IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1