OPIS PRODUKTU
SCHNEIDER ELECTRIC LV480817 - Air Circuit Breaker
The SCHNEIDER ELECTRIC LV480817 is a Masterpact MTZ2 series Air Circuit Breaker (ACB) engineered for the protection and control of low-voltage electrical distribution systems. This device integrates MicroLogic X control technology, providing precise overcurrent, short-circuit, and ground fault protection for industrial infrastructure, commercial buildings, and data center applications. It ensures operational continuity and system reliability in critical power distribution environments.
Technical Specifications:
- SERIES/FAMILY: Masterpact MTZ2
- COMPONENT TYPE: Air Circuit Breaker (ACB)
- ELECTRICAL SPECS:
- RATED CURRENT (In): 800A
- RATED OPERATIONAL VOLTAGE (Ue): Up to 690VAC
- RATED INSULATION VOLTAGE (Ui): 1000VAC
- RATED IMPULSE WITHSTAND VOLTAGE (Uimp): 12kV
- BREAKING CAPACITY (Icu): 65kA at 400/415VAC (H1 level)
- FREQUENCY: 50/60 Hz
- POLES: 3-pole or 4-pole configuration
- MECHANICAL/PHYSICAL:
- FRAME SIZE: MTZ2 08
- MOUNTING TYPE: Fixed or withdrawable (configuration dependent)
- OPERATION: Manual or electrical (motorized option)
- INTERFACE/CONTROL:
- CONTROL UNIT: MicroLogic X (e.g., 5.0 X, 6.0 X, 7.0 X)
- PROTECTION FUNCTIONS: Overload (long time), Short-circuit (short time, instantaneous), Ground fault/Earth leakage
- COMMUNICATION PROTOCOLS: Modbus, Modbus TCP/IP, Ethernet/IP, PROFINET (via optional communication modules)
- I/O: Auxiliary contacts, trip indication, remote control inputs (configurable)
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP40 (front face, within enclosure)
- POLLUTION DEGREE: 3
- OPERATING TEMPERATURE: -25°C to +70°C
- COOLING METHOD: Natural convection
- MOUNTING POSITION: Vertical or horizontal
- COMPATIBILITY/APPLICATION: Low-voltage power distribution, main incoming, sub-distribution, motor control centers, generator protection, data centers, industrial facilities, commercial buildings.