OPIS PRODUKTU
SCHNEIDER ELECTRIC LV833682SP - Air Circuit Breaker
The SCHNEIDER ELECTRIC LV833682SP is a MasterPact MTZ2 series air circuit breaker engineered for high-current electrical distribution and protection within industrial and commercial power systems. It integrates a Micrologic 6.0 X electronic trip unit, providing comprehensive overcurrent, short-circuit, and ground fault protection for enhanced system reliability and selective coordination. This fixed-mount, 3-pole device is specifically designed for main incoming, sub-distribution, and critical load protection applications requiring robust fault interruption capabilities.
Technical Specifications:
- SERIES/FAMILY: MasterPact MTZ2
- COMPONENT TYPE: Air Circuit Breaker (ACB)
- ELECTRICAL SPECS:
- NOMINAL CURRENT: 3600A
- POLES: 3P
- OPERATIONAL VOLTAGE: 690VAC (maximum)
- RATED INSULATION VOLTAGE: 1000V AC
- RATED IMPULSE WITHSTAND VOLTAGE: 12kV
- BREAKING CAPACITY (Icu): 85kA at 400/415VAC
- FREQUENCY: 50/60 Hz
- MECHANICAL/PHYSICAL:
- FRAME SIZE: MTZ2
- MOUNTING TYPE: Fixed
- OPERATION: Manual (motorized operation available with optional accessories)
- INTERFACE/CONTROL:
- TRIP UNIT: Micrologic 6.0 X (M2C)
- PROTECTION FUNCTIONS: Long-time (overload), Short-time, Instantaneous, Ground Fault
- COMMUNICATION: Modbus (via optional communication module)
- INDICATORS: Local status LEDs, LCD display on trip unit
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20 (front face)
- COOLING METHOD: Natural air convection
- OPERATING TEMPERATURE: -25 to 70 degrees C
- COMPATIBILITY/APPLICATION:
- TARGET SYSTEMS: Main and sub-distribution switchboards, motor control centers, critical power systems, data centers, industrial plants
- STANDARDS: IEC 60947-2