OPIS PRODUKTU
SCHNEIDER ELECTRIC METSEPM5350 - Advanced Power and Energy Meter
The SCHNEIDER ELECTRIC METSEPM5350 is an advanced PowerLogic PM5000 series power and energy meter designed for comprehensive electrical parameter measurement, monitoring, and analysis in industrial and commercial environments. This device integrates precise energy metering with power quality analysis capabilities, utilizing embedded microprocessor technology for data acquisition and processing. It is engineered for critical power applications, energy management systems, and cost allocation within facilities requiring detailed insight into electrical consumption and network health.
Technical Specifications:
- SERIES/FAMILY: PowerLogic PM5000 Series
- COMPONENT TYPE: Advanced Power and Energy Meter
- ELECTRICAL SPECS:
- NOMINAL VOLTAGE INPUT: Up to 690V AC L-L (direct connection) configurable via Voltage Transformers (VTs) for higher voltages
- NOMINAL CURRENT INPUT: Via Current Transformers (CTs), 5A or 1A secondary
- PHASE CONFIGURATION: 3-phase, 4-wire 3-phase, 3-wire 1-phase, 2-wire 1-phase, 3-wire
- FREQUENCY: 50/60 Hz
- ACTIVE ENERGY ACCURACY: Class 0.2S per IEC 62053-22
- MEASUREMENT PARAMETERS: Voltage (L-L, L-N), Current, Frequency, Active Power (kW), Reactive Power (kVAR), Apparent Power (kVA), Power Factor, Energy (kWh, kVARh, kVAh), Total Harmonic Distortion (THD) for V and I, Individual Harmonics up to 63rd
- MECHANICAL/PHYSICAL:
- FORM FACTOR: Panel mount
- CUTOUT DIMENSIONS: 92 x 92 mm (standard 96x96mm DIN panel cutout)
- DISPLAY: Backlit LCD graphical display
- INTERFACE/CONTROL:
- COMMUNICATION PROTOCOLS: Ethernet (Modbus TCP/IP, BACnet/IP), RS-485 (Modbus RTU)
- DIGITAL INPUTS: 4 (for status monitoring or tariff switching)
- DIGITAL OUTPUTS: 2 (for pulse output or alarm indication)
- DATA LOGGING: Onboard memory for historical data, alarms, and events
- ENVIRONMENTAL/MOUNTING:
- IP RATING (FRONT PANEL): IP52
- IP RATING (REAR): IP30
- COOLING METHOD: Natural convection
- MOUNTING STYLE: Flush panel mount
- COMPATIBILITY/APPLICATION: Energy Management Systems (EMS), Building Management Systems (BMS), SCADA systems, power quality monitoring, sub-billing, demand-side management, industrial process control, data centers, commercial buildings.