This SCHNEIDER ELECTRIC TeSys D series contactor, identified by code 33828, is an electromechanical switching device engineered for robust control of three-phase AC motors and resistive loads in industrial environments. It features a 3-pole power circuit with a 24V DC control coil, designed for integration into motor control centers, HVAC systems, pumping stations, and general machinery requiring reliable power switching up to 15 kW at 400V. Its design adheres to AC-3 utilization categories, ensuring suitability for motor starting and stopping under load.
Technical Specifications:
- SERIES/FAMILY: TeSys D
- COMPONENT TYPE: Contactor
- ELECTRICAL SPECS:
- POLES: 3P
- NOMINAL OPERATIONAL CURRENT (AC-3): 32 A at <= 440 V AC
- NOMINAL OPERATIONAL CURRENT (AC-1): 50 A at <= 440 V AC
- MOTOR POWER (AC-3): 15 kW at 380-400 V AC 18.5 kW at 415-440 V AC 18.5 kW at 500 V AC 18.5 kW at 660-690 V AC 7.5 kW at 220-230 V AC
- CONTROL CIRCUIT VOLTAGE: 24 V DC
- RATED INSULATION VOLTAGE: 690 V (IEC 60947-4-1)
- RATED IMPULSE WITHSTAND VOLTAGE: 6 kV (IEC 60947)
- OPERATIONAL FREQUENCY: 25...400 Hz
- MECHANICAL/PHYSICAL:
- POWER CONTACT CONFIGURATION: 3 NO (Normally Open)
- AUXILIARY CONTACT CONFIGURATION: 1 NO (Normally Open) + 1 NC (Normally Closed)
- FORM FACTOR: Compact, modular
- WEIGHT: Approximately 0.37 kg
- INTERFACE/CONTROL:
- CONTROL TYPE: Electromechanical DC coil
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20 (Front Face)
- AMBIENT AIR TEMPERATURE FOR OPERATION: -5 to 60 degrees C
- COOLING METHOD: Natural convection
- MOUNTING STYLE: Plate or 35 mm DIN rail
- COMPATIBILITY/APPLICATION:
- TARGET APPLICATIONS: Motor control, resistive load switching, HVAC systems, pumping applications, material handling, general industrial machinery.