DESCRIZIONE PRODOTTO
SCHNEIDER ELECTRIC 47295 - Thermal Overload Relay
The SCHNEIDER ELECTRIC 47295 is a TeSys LRD series thermal overload relay designed for the protection of AC motor circuits against overload and phase failure. This electromechanical device integrates bimetallic thermal sensing technology to provide reliable current-dependent tripping, ensuring operational continuity and equipment longevity in industrial control applications. It is specifically engineered for direct mounting onto TeSys D contactors, facilitating compact and integrated motor starter solutions in systems such as HVAC, pumping, and conveying.
Technical Specifications:
- SERIES/FAMILY: TeSys LRD
- COMPONENT TYPE: Thermal Overload Relay
- ELECTRICAL SPECS:
- CURRENT RANGE: 1.6 - 2.5 A
- POLES: 3
- TRIPPING CLASS: 10A
- AUXILIARY CONTACTS: 1 Normally Open (NO) + 1 Normally Closed (NC)
- RATED INSULATION VOLTAGE: 690V AC
- RATED IMPULSE WITHSTAND VOLTAGE: 6 kV
- MECHANICAL/PHYSICAL:
- RESET TYPE: Manual or Automatic
- MOUNTING: Direct mounting under TeSys D contactor, or independent with specific terminal block
- COMPATIBLE CONTACTORS: TeSys D series (LC1D09 to LC1D38)
- INTERFACE/CONTROL:
- PROTECTION FUNCTION: Overload, Phase Failure
- INDICATORS: Trip indicator
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20
- OPERATING TEMPERATURE: -20 to 60 degrees C
- COOLING METHOD: Natural convection
- COMPATIBILITY/APPLICATION:
- APPLICATION: Motor protection in industrial control panels, HVAC systems, pumping stations, material handling equipment, and general machinery.
- STANDARDS: IEC 60947-4-1, IEC 60947-5-1