DESCRIZIONE PRODOTTO
SCHNEIDER ELECTRIC A9N18595 - Miniature Circuit Breaker
The SCHNEIDER ELECTRIC A9N18595 is a single-pole Miniature Circuit Breaker (MCB) from the Acti 9 iC60N series, engineered for overcurrent and short-circuit protection in low-voltage electrical distribution systems. This modular device provides thermal-magnetic tripping characteristics, conforming to IEC/EN 60898-1 and IEC/EN 60947-2 standards, making it suitable for diverse applications including residential, commercial, and light industrial panel boards. It ensures circuit integrity and equipment safety by rapidly disconnecting power upon fault detection.
Technical Specifications:
- SERIES/FAMILY: Acti 9 iC60N
- COMPONENT TYPE: Miniature Circuit Breaker (MCB)
- ELECTRICAL SPECS:
- POLES: 1P
- RATED CURRENT (In): 25A
- TRIP CURVE: C (Thermal-magnetic, for general purpose protection of resistive and inductive loads with low inrush current)
- RATED OPERATIONAL VOLTAGE (Ue): 230/400V AC
- RATED INSULATION VOLTAGE (Ui): 500V AC
- RATED IMPULSE WITHSTAND VOLTAGE (Uimp): 6kV
- RATED SHORT-CIRCUIT BREAKING CAPACITY (Icn): 6kA at 230/400V AC (IEC/EN 60898-1)
- RATED ULTIMATE SHORT-CIRCUIT BREAKING CAPACITY (Icu): 10kA at 230V AC (IEC/EN 60947-2)
- FREQUENCY: 50/60 Hz
- MECHANICAL/PHYSICAL:
- MODULAR WIDTH: 18mm (1 module)
- TERMINAL TYPE: Tunnel terminals (top and bottom)
- TERMINAL CAPACITY: Up to 35mm² rigid, 25mm² flexible
- ELECTRICAL ENDURANCE: 20000 cycles
- MECHANICAL ENDURANCE: 20000 cycles
- INTERFACE/CONTROL:
- INDICATORS: Trip indicator, contact position indicator (red/green)
- CONTROL TYPE: Toggle switch (manual operation)
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20 (terminals), IP40 (in enclosure)
- OPERATING TEMPERATURE: -35°C to +70°C
- STORAGE TEMPERATURE: -40°C to +85°C
- MOUNTING STYLE: DIN rail (35mm symmetrical)
- POLLUTION DEGREE: 3
- COMPATIBILITY/APPLICATION:
- STANDARDS: IEC/EN 60898-1, IEC/EN 60947-2
- APPLICATION: Overcurrent and short-circuit protection for electrical circuits in residential, commercial, and industrial installations. Suitable for resistive and inductive loads with moderate inrush currents.