DESCRIZIONE PRODOTTO
SCHNEIDER ELECTRIC LV833616 - Molded Case Circuit Breaker (MCCB) with Electronic Trip Unit
This device is a SCHNEIDER ELECTRIC Compact NSXm series molded case circuit breaker, engineered for low voltage electrical distribution systems. It integrates a Micrologic 4.2 Vigi electronic trip unit, providing comprehensive protection against overload, short-circuit, and earth leakage faults. Designed for industrial and commercial applications, this MCCB ensures critical circuit protection and operational continuity in switchboards and control panels.
Technical Specifications:
- SERIES/FAMILY: Compact NSXm
- COMPONENT TYPE: Molded Case Circuit Breaker (MCCB)
- ELECTRICAL SPECS:
- RATED CURRENT (In): 160A
- NUMBER OF POLES: 3
- PROTECTION POLES: 3D (3 Protected Poles)
- BREAKING CAPACITY (Icu): 36kA at 400/415VAC
- RATED OPERATIONAL VOLTAGE (Ue): 220/240VAC to 690VAC
- RATED INSULATION VOLTAGE (Ui): 800V
- RATED IMPULSE WITHSTAND VOLTAGE (Uimp): 8kV
- FREQUENCY: 50/60 Hz
- MECHANICAL/PHYSICAL:
- FRAME SIZE: 160A Frame
- MOUNTING TYPE: Fixed, on DIN rail or mounting plate
- TERMINAL TYPE: EverLink Power Terminals
- FORM FACTOR: Compact, modular design
- INTERFACE/CONTROL:
- TRIP UNIT TYPE: Micrologic 4.2 Vigi Electronic Trip Unit
- PROTECTION FUNCTIONS: Long-time (Overload), Short-time (Short-circuit), Instantaneous (Short-circuit), Earth Leakage (Vigi)
- ADJUSTABILITY: Adjustable Long-Time Delay, Adjustable Short-Time Delay, Adjustable Instantaneous Threshold, Adjustable Earth Leakage Sensitivity and Time Delay
- INDICATORS: Trip Indication, Earth Leakage Indication
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP40 (Front Face with Escutcheon)
- COOLING METHOD: Natural Convection
- MOUNTING STYLE: Fixed, DIN Rail or Plate Mountable
- OPERATING TEMPERATURE RANGE: -25 to 70 degrees C
- COMPATIBILITY/APPLICATION: Low Voltage Electrical Distribution, Motor Protection, Generator Protection, Industrial Switchboards, Commercial Building Installations, Sub-distribution Panels