DESCRIZIONE PRODOTTO
SCHNEIDER ELECTRIC LV850006X - Air Circuit Breaker Frame
The SCHNEIDER ELECTRIC LV850006X is a Masterpact MTZ2 series air circuit breaker frame, engineered for high-current electrical distribution protection in demanding industrial and commercial environments. This component provides robust short-circuit and overload protection, serving as the foundational element for integration with advanced MicroLogic X trip units. It is specifically designed for main and sub-main low voltage power distribution applications, including switchboards, motor control centers, and critical power infrastructure.
Technical Specifications:
- SERIES/FAMILY: Masterpact MTZ2
- COMPONENT TYPE: Air Circuit Breaker Frame
- ELECTRICAL SPECS:
- NOMINAL CURRENT (In): 5000 A
- RATED OPERATIONAL VOLTAGE (Ue): 690 VAC
- RATED INSULATION VOLTAGE (Ui): 1000 VAC
- RATED IMPULSE WITHSTAND VOLTAGE (Uimp): 12 kV
- BREAKING CAPACITY (Icu): 65 kA at 400/415 VAC (H1 level)
- NUMBER OF POLES: 4P
- FREQUENCY: 50/60 Hz
- MECHANICAL/PHYSICAL:
- FRAME SIZE: MTZ2 (5000A frame)
- MOUNTING TYPE: Fixed (standard configuration withdrawable options available with specific part numbers)
- CONNECTION TYPE: Rear connection
- INTERFACE/CONTROL:
- TRIP UNIT COMPATIBILITY: Designed for MicroLogic X series electronic trip units (e.g., MicroLogic 5.0 X, 6.0 X, 7.0 X)
- COMMUNICATION CAPABILITY: Supports Modbus, Ethernet, PROFINET, PROFIBUS via optional communication modules when equipped with a MicroLogic X trip unit
- PROTECTION FUNCTIONS: Overload (long-time), Short-circuit (short-time, instantaneous), Ground fault, Residual current (functions dependent on installed MicroLogic X trip unit)
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20 (with front cover)
- COOLING METHOD: Natural convection
- OPERATING TEMPERATURE: -25 to 70 degrees C
- COMPATIBILITY/APPLICATION:
- TARGET SYSTEMS: Main and sub-main low voltage power distribution panels, switchboards, motor control centers (MCCs)
- APPLICATIONS: Industrial facilities, data centers, hospitals, commercial buildings, critical power infrastructure, renewable energy systems