DESCRIZIONE PRODOTTO
SCHNEIDER ELECTRIC M9F52102 - Miniature Circuit Breaker
This device is a 2-pole miniature circuit breaker from the SCHNEIDER ELECTRIC Acti9 iC60N series, engineered for overcurrent and short-circuit protection in industrial and commercial electrical distribution systems. It features a C-type thermal-magnetic tripping mechanism, providing reliable protection for resistive and inductive loads with moderate inrush currents. Designed for DIN rail mounting, it ensures circuit integrity and operational safety in control panels, machinery, and building infrastructure.
Technical Specifications:
- SERIES/FAMILY: Acti9 iC60N
- COMPONENT TYPE: Miniature Circuit Breaker (MCB)
- ELECTRICAL SPECS:
- NOMINAL CURRENT: 10 A
- POLES: 2P
- NOMINAL OPERATIONAL VOLTAGE (Ue): 230/400 VAC
- FREQUENCY: 50/60 Hz
- RATED INSULATION VOLTAGE (Ui): 500 VAC
- RATED IMPULSE WITHSTAND VOLTAGE (Uimp): 6 kV
- BREAKING CAPACITY (Icn): 6 kA at 230/400 VAC
- TRIPPING CURVE: C-curve (5 to 10 In)
- MECHANICAL/PHYSICAL:
- MOUNTING: DIN Rail (35mm symmetrical rail)
- TERMINALS: Tunnel type terminals (top and bottom)
- CABLE CAPACITY: 1 to 25 mm2 (flexible), 1 to 35 mm2 (rigid)
- WIDTH: 2 x 9mm modules (36mm total)
- INTERFACE/CONTROL:
- PROTECTION TYPE: Thermal-magnetic overcurrent and short-circuit protection
- INDICATORS: Mechanical trip indicator (red/green window)
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20 (terminals), IP40 (front face in enclosure)
- OPERATING TEMPERATURE: -35 to 70 degrees C
- STORAGE TEMPERATURE: -40 to 85 degrees C
- POLLUTION DEGREE: 3
- ALTITUDE: 0 to 2000 m without derating
- COMPATIBILITY/APPLICATION:
- APPLICATIONS: Overcurrent and short-circuit protection for resistive and inductive loads, lighting circuits, socket outlets, and control circuits.
- TARGET SYSTEMS: Industrial control panels, commercial distribution boards, building infrastructure.
- STANDARDS: IEC/EN 60898-1, IEC/EN 60947-2