ASEA BROWN BOVERI 1SDA066638R1 - Molded Case Circuit Breaker
This device is a SACE Tmax XT2N series Molded Case Circuit Breaker, engineered for overcurrent and short-circuit protection in industrial and commercial electrical distribution systems. It integrates a fixed thermal-magnetic trip unit, providing reliable protection for three-phase circuits and equipment. Designed for fixed installation, it ensures operational continuity and safety in applications such as motor control centers, panel boards, and switchgear.
Technical Specifications:
- SERIES/FAMILY: SACE Tmax XT2N
- COMPONENT TYPE: Molded Case Circuit Breaker (MCCB)
- ELECTRICAL SPECS:
- NOMINAL CURRENT (In): 160 A
- NUMBER OF POLES: 3
- RATED OPERATIONAL VOLTAGE (Ue): Up to 690 VAC
- RATED INSULATION VOLTAGE (Ui): 1000 V
- RATED IMPULSE WITHSTAND VOLTAGE (Uimp): 8 kV
- RATED ULTIMATE SHORT-CIRCUIT BREAKING CAPACITY (Icu): 36 kA at 400/415 VAC 25 kA at 480 VAC 10 kA at 690 VAC
- RATED SERVICE SHORT-CIRCUIT BREAKING CAPACITY (Ics): 100% of Icu
- FREQUENCY: 50/60 Hz
- MECHANICAL/PHYSICAL:
- TRIP UNIT TYPE: TMD (Thermal-Magnetic Fixed)
- MOUNTING TYPE: Fixed
- TERMINAL TYPE: Front Terminals
- INTERFACE/CONTROL:
- PROTECTION FUNCTIONS: Overload (Thermal), Short-Circuit (Magnetic)
- ADJUSTABILITY: Fixed thermal and magnetic settings
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20 (Terminals), IP30 (Front with cover)
- COOLING METHOD: Natural Air Convection
- OPERATING TEMPERATURE: -25 to +70 degrees C
- COMPATIBILITY/APPLICATION:
- TARGET SYSTEMS: Industrial and commercial electrical distribution, motor control centers, panel boards, switchgear
- PROTECTED LOADS: General loads, motors, transformers, cables