ОПИСАНИЕ ПРОДУКТА
MITSUBISHI R08SFCPU-SET - Safety CPU Module
The MITSUBISHI R08SFCPU-SET is a dedicated safety CPU module within the MELSEC iQ-R Series programmable automation controller platform. This specific designation typically indicates a complete package for operational deployment, often including necessary memory cards or licenses. It provides integrated safety control for industrial machinery, enabling compliance with international safety standards through deterministic processing of safety-related inputs and outputs. This module is engineered for applications requiring high-integrity safety functions, such as emergency stop systems, safety interlocks, and protective device monitoring in manufacturing, robotics, and process control environments.
Technical Specifications:
- SERIES/FAMILY: MELSEC iQ-R Series
- COMPONENT TYPE: Safety Programmable Logic Controller (PLC) CPU Module
- PROGRAM CAPACITY: 80K steps (Safety Program)
- PROCESSING SPEED: 0.34 ms (for 1K steps safety program)
- ELECTRICAL SPECS:
- POWER CONSUMPTION: 0.8 A (5VDC internal current consumption from base unit)
- SUPPLY VOLTAGE: Internal 5VDC supplied by iQ-R Series base unit
- MECHANICAL/PHYSICAL:
- FORM FACTOR: Single-slot rack-mounted module
- MOUNTING: Installs into MELSEC iQ-R Series base unit
- INTERFACE/CONTROL:
- PROGRAMMING PORT: USB, Ethernet (RJ45)
- NETWORK INTERFACES: Utilizes iQ-R Series network modules for industrial network communication (e.g., CC-Link IE Field Network, EtherNet/IP, PROFINET)
- SAFETY COMMUNICATION: Integrated safety communication over standard industrial networks via compatible safety I/O modules and network interfaces
- SAFETY FUNCTIONS: Supports implementation of safety functions including Emergency Stop, Safety Gate, Light Curtain, Two-Hand Control, Muting, Speed Monitoring
- SAFETY INTEGRITY LEVEL (SIL): SIL 3 per IEC 61508, IEC 62061
- PERFORMANCE LEVEL (PL): PLe per ISO 13849-1
- CATEGORY: Category 4 per ISO 13849-1
- ENVIRONMENTAL/MOUNTING:
- IP RATING: Module is for internal cabinet mounting IP rating depends on enclosure
- OPERATING TEMPERATURE: 0 to 55 degrees Celsius
- OPERATING HUMIDITY: 5 to 95% RH (non-condensing)
- COOLING METHOD: Natural convection
- COMPATIBILITY/APPLICATION:
- TARGET SYSTEMS: MITSUBISHI MELSEC iQ-R Series automation platforms
- APPLICATIONS: Functional safety control in manufacturing, robotics, material handling, presses, and process industries
- STANDARDS COMPLIANCE: IEC 61508, IEC 62061, ISO 13849-1, UL/cUL, CE, KC