ОПИСАНИЕ ПРОДУКТА
PEPPERL & FUCHS 084008 - KFD2-SR2-EX1.W.SM Safety Relay / Switch Amplifier
PEPPERL & FUCHS 084008 is a KFD2-SR2-EX1.W.SM safety relay and switch amplifier from the K-System series, engineered for signal conditioning and galvanic isolation of intrinsically safe circuits. It provides two independent channels for monitoring NAMUR sensors or mechanical contacts located in hazardous areas, converting their signals into potential-free relay outputs for use in safe area control systems. This module is designed for applications requiring high functional safety and reliable operation in process automation and safety instrumented systems.
Technical Specifications:
- SERIES/FAMILY: K-System, KFD2 Series
- COMPONENT TYPE: Safety Relay / Switch Amplifier (Intrinsically Safe Barrier)
- ELECTRICAL SPECS:
- SUPPLY VOLTAGE: 20-35 VDC (Wide Power Range)
- INPUT: 2-channel, Intrinsically Safe, for NAMUR sensors or mechanical contacts
- OUTPUT: 2 x Potential-free Relay Outputs (SPDT changeover contacts)
- SWITCHING CAPACITY: 250 VAC / 2 A / 500 VA 30 VDC / 2 A / 60 W
- INTERFACE/CONTROL:
- INPUT SIGNAL: NAMUR proximity switches (EN 60947-5-6) or dry contacts
- OUTPUT SIGNAL: Relay contact closure
- SAFETY INTEGRITY LEVEL (SIL): Up to SIL 2 (IEC/EN 61508)
- DIAGNOSTICS: Line fault detection (open and short circuit)
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20
- MOUNTING: 35 mm DIN rail mounting
- TERMINALS: Screw terminals (SM)
- HAZARDOUS AREA CERTIFICATION: ATEX, IECEx for intrinsically safe input circuits (e.g., Ex ia IIC T4 Ga)
- OPERATING TEMPERATURE: -20 to +60 °C
- COMPATIBILITY/APPLICATION:
- TARGET SYSTEMS: Safety Instrumented Systems (SIS), Emergency Shutdown (ESD) systems, Process Control Systems
- APPLICATIONS: Monitoring of limit switches, proximity sensors, and pushbuttons in hazardous locations (Zone 0, 1, 2)