ОПИСАНИЕ ПРОДУКТА
PEPPERL & FUCHS 181114 - K-System Single Channel Solenoid Driver / Alarm Driver Isolated Barrier
PEPPERL & FUCHS 181114 is a K-System single-channel isolated barrier engineered for controlling devices in hazardous areas from a safe area control system. This module provides intrinsic safety for solenoid valves, alarms, and LEDs, ensuring reliable operation and compliance with international hazardous area standards. It features galvanic isolation and line fault detection for enhanced system integrity in process automation applications.
Technical Specifications:
- SERIES/FAMILY: K-System (KFD2-CD-EX1.PN)
- COMPONENT TYPE: Single Channel Solenoid Driver / Alarm Driver Isolated Barrier
- ELECTRICAL SPECS:
- SUPPLY VOLTAGE: 20-35VDC (Nominal 24VDC)
- POWER CONSUMPTION: < 1.5W
- SAFE AREA INPUT: Digital input from control system (e.g., PLC)
- HAZARDOUS AREA OUTPUT: Intrinsically safe, short-circuit proof output
- OUTPUT CURRENT: Up to 50mA
- INTERFACE/CONTROL:
- ISOLATION: Galvanic isolation between input, output, and power supply
- DIAGNOSTICS: Line fault detection for open and short circuits
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20
- OPERATING TEMPERATURE: -20°C to +60°C
- MOUNTING: 35mm DIN rail mounting
- COMPATIBILITY/APPLICATION:
- HAZARDOUS AREA CLASSIFICATION: ATEX, IECEx, FM, cULus for Zone 0, 1, 2 / Division 1, 2
- TARGET SYSTEMS: Distributed Control Systems (DCS), Programmable Logic Controllers (PLC), Emergency Shutdown (ESD) systems
- FUNCTION: Drives intrinsically safe solenoid valves, alarms, and LEDs in hazardous locations