ОПИСАНИЕ ПРОДУКТА
PEPPERL & FUCHS 199793 - K-System Intrinsic Safety PROFINET Gateway / Solenoid Driver Barrier
This module is a K-System intrinsic safety barrier designed to integrate intrinsically safe field devices into PROFINET-based control systems. It functions as a PROFINET gateway, providing a single channel for controlling solenoid valves, sounders, or other actuators located in hazardous areas. The device ensures safe operation by limiting energy to field devices in accordance with Ex ia IIC requirements, facilitating robust and compliant process automation.
Technical Specifications:
- SERIES/FAMILY: K-System (KFD2)
- COMPONENT TYPE: Intrinsic Safety PROFINET Gateway / Solenoid Driver Barrier
- ELECTRICAL SPECS:
- SUPPLY VOLTAGE: 20-35 VDC
- POWER CONSUMPTION: Approximately 2.5 W
- OUTPUT TYPE: Intrinsically Safe Switched Output
- OUTPUT PARAMETERS (Ex ia IIC): Uo = 20.5 V, Io = 93 mA, Po = 0.48 W
- INTERFACE/CONTROL:
- CONTROL NETWORK: PROFINET IO (2x RJ45 ports for line topology)
- FIELD CONNECTION: 2-wire intrinsically safe output
- CONFIGURATION: GSDML file integration, PACTware for advanced diagnostics
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20
- MOUNTING: 35mm DIN Rail
- OPERATING TEMPERATURE: -20 °C to +60 °C
- HAZARDOUS AREA CERTIFICATION: [EPL Ga] IIC, [EPL Gb] IIB (for connected field devices)
- INSTALLATION ZONE: Safe area or Zone 2 (for the barrier module)
- COMPATIBILITY/APPLICATION:
- TARGET SYSTEMS: PROFINET-enabled Distributed Control Systems (DCS) and Programmable Logic Controllers (PLC)
- FIELD DEVICES: Intrinsically safe solenoid valves, sounders, beacons, and other actuators
- INDUSTRIES: Chemical processing, oil and gas, pharmaceuticals, water treatment, and other process industries requiring hazardous area control