PEPPERL & FUCHS 265685 - K-System Isolated Barrier, Frequency Converter
This K-System isolated barrier, identified as KFD2-CD-EX1.30, functions as a frequency converter for intrinsically safe applications. It is engineered to interface frequency-generating field devices located in hazardous areas with control systems in the safe area, providing galvanic isolation and converting pulse inputs into proportional analog current or voltage outputs. This device is critical for process automation, ensuring signal integrity and compliance with intrinsic safety standards in environments such as chemical processing, oil and gas, and pharmaceutical manufacturing.
Technical Specifications:
- SERIES/FAMILY: K-System (KFD2)
- COMPONENT TYPE: Isolated Barrier, Frequency Converter/Driver
- PART NUMBER: KFD2-CD-EX1.30
- INPUT SIGNAL: Frequency input from NAMUR sensors or mechanical contacts in hazardous areas
- OUTPUT SIGNAL: 0/4-20mA or 0-10V analog output to the safe area
- SUPPLY VOLTAGE: 20-35V DC (Nominal 24V DC)
- POWER CONSUMPTION: < 1.5W
- ISOLATION: Galvanic isolation between input, output, and power supply
- HAZARDOUS AREA CERTIFICATION: ATEX, IECEx, FM, cULus for intrinsic safety (e.g., [Ex ia Ga] IIC, [Ex ia Da] IIIC)
- CONFIGURATION: Configurable via DIP switches or PACTware/DTM software
- MOUNTING: 35mm DIN rail mount
- ENCLOSURE RATING: IP20
- OPERATING TEMPERATURE: -20°C to +60°C
- COMPATIBILITY/APPLICATION: Interfaces with DCS, PLC, and SCADA systems suitable for flow measurement, speed monitoring, and general frequency-to-analog conversion in intrinsically safe circuits.