ОПИСАНИЕ ПРОДУКТА
PEPPERL & FUCHS 281014 - KFD2-SR2-EX1.W.SM Safety Relay Switch Amplifier
This K-System series safety relay switch amplifier provides intrinsic safety for signals originating from hazardous areas. It conditions inputs from NAMUR sensors or mechanical contacts, offering galvanic isolation and converting them into a safe, fail-safe relay output for control systems. Certified for Safety Integrity Level (SIL) 3, it is engineered for critical safety instrumented functions in process automation and emergency shutdown systems.
Technical Specifications:
- SERIES/FAMILY: K-System, KFD2 Series
- COMPONENT TYPE: Switch Amplifier, Intrinsic Safety Barrier, Safety Relay
- ELECTRICAL SPECS:
- SUPPLY VOLTAGE: 20-35VDC (24VDC nominal)
- POWER CONSUMPTION: Approximately 1.5W
- INPUT: 2-wire NAMUR proximity switch (EN 60947-5-6) or dry contact from hazardous area
- OUTPUT: 1 x SPDT (Single Pole Double Throw) relay contact
- SWITCHING CAPACITY: 250VAC/125VDC, 2A resistive load
- ISOLATION: Galvanic isolation between input, output, and power supply
- INTERFACE/CONTROL:
- INPUT FUNCTION: Single channel, line fault detection (open/short circuit)
- OUTPUT FUNCTION: De-energized to trip (fail-safe)
- LED INDICATORS: Power, switching state, fault
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20
- OPERATING TEMPERATURE: -20 to +60 °C (-4 to +140 °F)
- MOUNTING: 35mm DIN rail
- HAZARDOUS AREA CERTIFICATION: ATEX, IECEx, FM, cULus for Zone 0, 1, 2 / Class I, Div 1, 2
- COMPATIBILITY/APPLICATION:
- SAFETY INTEGRITY LEVEL (SIL): Up to SIL 3 (IEC 61508/IEC 61511)
- PERFORMANCE LEVEL (PL): Up to PL e (ISO 13849)
- TARGET SYSTEMS: Safety Instrumented Systems (SIS), Emergency Shutdown (ESD), Fire and Gas (F&G) systems
- INPUT DEVICES: NAMUR sensors, mechanical contacts, limit switches in hazardous locations