ОПИСАНИЕ ПРОДУКТА
PEPPERL & FUCHS 301020 - Intrinsic Safety Barrier, Switch Amplifier
This is a single-channel intrinsic safety barrier from the K-System series, specifically the KFD2-SR2-EX1.W model, engineered for galvanic isolation and signal conditioning of discrete signals originating from hazardous areas. It functions as a switch amplifier, converting signals from NAMUR sensors or mechanical contacts into a safe, isolated relay output for control systems in the safe area, while incorporating comprehensive line fault detection.
Technical Specifications:
- SERIES/FAMILY: K-System, KFD2-SR2-EX1.W
- COMPONENT TYPE: Intrinsic Safety Barrier, Switch Amplifier
- ELECTRICAL SPECS:
- SUPPLY VOLTAGE: 20-35V DC (24V DC nominal)
- POWER CONSUMPTION: < 1.5W
- INPUT: NAMUR sensor (EN 60947-5-6) or dry contact
- OUTPUT: 1 x Potential-free relay contact (SPDT, changeover)
- SWITCHING CAPACITY: 250V AC / 2A / 500VA 125V DC / 2A / 60W (resistive load)
- INTERFACE/CONTROL:
- SIGNAL TYPE: Discrete (ON/OFF)
- FAULT DETECTION: Line fault detection (LFD) for open/short circuit on sensor input
- INDICATORS: LEDs for operation, switching state, and fault
- ENVIRONMENTAL/MOUNTING:
- HAZARDOUS AREA CERTIFICATION: Ex ia IIC T4 Ga (for connection to Zone 0/20), Ex ia IIB T4 Gb (for connection to Zone 1/21)
- IP RATING: IP20 (terminal side)
- OPERATING TEMPERATURE: -20 to +60 °C
- MOUNTING: 35mm DIN rail
- COMPATIBILITY/APPLICATION:
- APPLICATION: Isolation and signal conditioning for NAMUR proximity sensors, limit switches, and mechanical contacts in hazardous environments.
- TARGET SYSTEMS: Process control systems, safety instrumented systems (SIS), distributed control systems (DCS), programmable logic controllers (PLCs).