ОПИСАНИЕ ПРОДУКТА
PEPPERL & FUCHS 301064 - Intrinsically Safe Switch Amplifier
This K-System intrinsically safe isolated barrier, identified as KFD2-SR2-EX1.W, functions as a single-channel switch amplifier designed for the safe operation of loads in hazardous areas. It provides galvanic isolation between the hazardous and non-hazardous areas, enabling the connection of NAMUR proximity switches or mechanical contacts to control a relay output. Engineered for process automation, chemical, and oil & gas industries, it ensures compliance with intrinsic safety standards and maintains high system integrity.
Technical Specifications:
- SERIES/FAMILY: K-System (KFD2-SR2-EX1.W)
- COMPONENT TYPE: Intrinsically Safe Switch Amplifier, Single Channel
- ELECTRICAL SPECS:
- SUPPLY VOLTAGE: 20-35 VDC
- INPUT: NAMUR proximity switch (EN 60947-5-6) or dry contact from hazardous area
- OUTPUT: 1 x Relay (SPDT changeover contact)
- SWITCHING CAPACITY: 250 VAC / 2 A (cos phi > 0.7) 125 VDC / 0.5 A 30 VDC / 2 A
- INTERFACE/CONTROL:
- INPUT SIGNAL: Detects open and short circuit line faults
- INDICATORS: LEDs for operation, fault, and switching status
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20
- MOUNTING: 35 mm DIN rail
- OPERATING TEMPERATURE: -20°C to +60°C
- COMPATIBILITY/APPLICATION:
- HAZARDOUS AREA CERTIFICATIONS: ATEX, IECEx, cULus
- SAFETY INTEGRITY LEVEL (SIL): Up to SIL 2 (IEC/EN 61508)
- TARGET APPLICATIONS: Process control systems requiring intrinsic safety for field devices in Zone 0, 1, 2