ОПИСАНИЕ ПРОДУКТА
PEPPERL & FUCHS 3261610136 - Intrinsically Safe Solenoid Driver Barrier
This single-channel intrinsically safe isolation barrier from the PEPPERL & FUCHS K-System series is engineered for controlling solenoid valves, I/P converters, and positioners situated in hazardous areas. It provides galvanic isolation and precisely limits energy to intrinsically safe levels, ensuring reliable and compliant operation of field devices from a safe area control system. This module is designed for critical process control applications requiring ATEX and IECEx certification.
Technical Specifications:
- SERIES/FAMILY: K-System (KFD2)
- COMPONENT TYPE: Intrinsically Safe Solenoid Driver / Positioner Control Barrier
- ELECTRICAL SPECS:
- SUPPLY VOLTAGE: 24VDC nominal (20V to 35VDC operating range)
- POWER CONSUMPTION: Approximately 1.5W
- OUTPUT TYPE: Intrinsically safe, current-limited output for driving solenoid valves, I/P converters, and positioners
- CHANNELS: 1-channel
- INTERFACE/CONTROL:
- SAFE AREA INPUT: Control input from PLC/DCS (e.g., switch contact, voltage signal)
- HAZARDOUS AREA OUTPUT: Intrinsically safe output to field device (e.g., solenoid, I/P converter)
- DIAGNOSTICS: Front panel LED indicators for power, output status, and fault conditions
- ENVIRONMENTAL/MOUNTING:
- IP RATING: IP20
- MOUNTING: 35mm DIN rail
- OPERATING TEMPERATURE: -20°C to +60°C
- COMPATIBILITY/APPLICATION:
- HAZARDOUS AREA CLASSIFICATION: Certified for use in Zone 0, 1, 2 (Gas) and Zone 20, 21, 22 (Dust) environments
- FIELD DEVICES: Intrinsically safe solenoid valves, I/P converters, electro-pneumatic positioners
- CONTROL SYSTEMS: Compatible with PLC, DCS, and safety instrumented systems
- SAFETY INTEGRITY LEVEL: Suitable for applications up to SIL 2 (IEC 61508)